Application guidelines
Installer reference guide
35
EPGA11~ EAV23DA6V
Daikin Altherma 3 H F
4P606487-1 – 2019.12
Setting
Value
Number of water temperature zones:
▪
#: [4.4]
▪
Code: [7-02]
0 (
Single zone
): Main
5.2.3 Multiple rooms – Two LWT zones
In this document:
▪
Main zone = Zone with the lowest design temperature in heating, and the highest
design temperature in cooling
▪
Additional zone = Zone with the highest design temperature in heating, and the
lowest design temperature in cooling
CAUTION
If there is more than one leaving water zone, ALWAYS install a mixing valve station in
the main zone to decrease (in heating)/increase (in cooling) the leaving water
temperature when the additional zone has demand.
Typical example:
Room (zone)
Heat emitters: Design temperature
Living room (main zone)
Underfloor heating:
▪
In heating: 35°C
▪
In cooling: 20°C (only refreshment, no
real cooling allowed)
Bed rooms (additional zone)
Heat pump convectors:
▪
In heating: 45°C
▪
In cooling: 12°C
Setup
B
A
E
C
D
a
b
a
c
d
A
Additional leaving water temperature zone
B
Room 1
C
Room 2
D
Main leaving water temperature zone
E
Room 3
a
Remote controller of the heat pump convectors