ENGLISH
92
GB
11
Low pressure signal input NC,
automatic and manual reset
F4
12
Low pressure input NO only manual
reset
F4
13
Low pressure input NC only manual
reset
F4
7.6.15.1 - Disabling the functions associated with the input
Setting 0 as the configuration value of an input, each function associated
with the input will be disabled irrespective of the signal present on the input
terminals.
7.6.15.2 - Setting external float function
The external float can be connected to any input, for the electrical connec
-
tions refer to the control unit manual.
The float function is obtained, setting one of the values in Table 16 on the
parameter Ix, for the input to which the float has been connected.
The activation of the external float function generates the block of the sys
-
tem. The function is conceived for connecting the input to a signal arriving
from a float which indicates lack of water.
When this function is active the float switch symbol is shown on the STA
-
TUS line of the main page.
For the system to block and give the error signal F1, the input must be
activated for at least 1 sec.
When it is in error condition F1, the input must have been deactivated for
at least 30 sec before the system can be unblocked. The behaviour of the
function is summed up in Table 15.
When several float functions are configured at the same time on different
inputs, the system will indicate F1 when at least one function is activated
and will remove the alarm when none is activated.
Table 14: Configurations of the digital inputs
Behaviour of the external float function depending on INx and on the input
Value of
Parameter
Ix
Input configu
-
ration
Input status
Operation
Shown on
display
1
Active with high
signal on input
(NO)
Absent
Normal
None
Present
System block
for water lack by
external float
F1
2
Active with low
signal on input
(NC)
Absent
System block
for water lack by
external float
F1
Present
Normal
None
7.6.15.3 - Setting auxiliary setpoint input function
The signal that enables an auxiliary setpoint can be supplied on any of the
4 inputs (for the electrical connections, refer to the control unit manual).
The auxiliary setpoint is obtained by setting the Ix parameter relating to the
input on which the connection has been made, in accordance with Table
17. Example:. to use Paux 2, set I2 on 3 or 4 and use input 2 on the control
unit; in this condition, if input 2 is energized, pressure Paux 2 will be pro
-
duced and the display will show P2.
The auxiliary setpoint function modifies the system setpoint from pressure
SP (see par. 7.3 – Setpoint Menu ) to pressure Pi, where is represents the
input used. In this way, as well as SP, four other pressures are available,
P1, P2, P3, P4.
When this function is active the symbol Pi is shown on the main page.
For the system to work with the auxiliary setpoint, the input must be active
for at least 1 sec.
When you are working with the auxiliary setpoint, to return to working with
setpoint SP, the input must not be active for at least 1 sec. The behaviour
of the function is summed up in Table 16.
Table 15: External float function
Summary of Contents for E.sybox 50
Page 6: ......
Page 59: ...ITALIANO IT 56...
Page 62: ......
Page 116: ......
Page 172: ......
Page 228: ......
Page 284: ......
Page 285: ...RU 282 IEC 364 CEI 64 2 1000 3 1 2 e sybox e sybox 30 50 e sybox...
Page 286: ...RU 283 6 1 A 2 2 3 1 2 3 4 5 6 B 10 3 C 4 4 2 1 IN 2 3 1 A B C D E F A B E F 1...
Page 287: ...RU 284 OUT D 1 OUT C 4 4 1 2 F 1 2 2 3 IN C 2 4 5 4 4 5 4 5 5 1 1 SP 3 0 RP 0 3 5 6 7...
Page 291: ...RU 288 10 E 270 200 2 1 1 F IN 7 F OUT 7 1 GAS 1 3 1 BSP 25 8 2 1 2 30 25 mm 25 mm 8...
Page 293: ...RU 290 2 2 1 IN 9 OUT 9 D OUT 2 9 2 1 GAS 8 2 2 2 90 10 4 4 10...
Page 294: ...RU 291 2 2 3 3_ 5 F 1 1 5 11 x4 x4 1 5 F 1 3 _ 5 3 8 8 e sybox 7 e sybox30 50 3 1...
Page 301: ...RU 298 6 128x240 POWER COMM ALARM 12 6 MODE 1 SET 12 3 EEprom SET 6 SET MODE 5 5 6...
Page 302: ...RU 299 5 5 5 2 2 7 8 1 2 6 1 MODE SET MODE 7 2 2...
Page 304: ...RU 301 FF AY AE AF I1 1 I2 2 I3 3 I4 4 O1 1 O2 2 FW RF PW...
Page 305: ...RU 302 6 2 14 MODE 8 8 15 14 13...
Page 306: ...RU 303 2 298 9 GO SB DIS F1 F3 F4 P1 1 P2 2 P3 3 P4 4 EE EEprom 9 6 3 14...
Page 307: ...RU 304 GO SB 15 15 10 6 4 PW 6 5 RF PW 7 7 1 MODE MODE 7 1 1 7 1 2 RS 7 1 3 VP 7 1 4 VF...
Page 308: ...RU 305 7 1 9 11 SB F 8 F SB 7 1 10 2 11 7 1 5 PO PO 7 1 6 C1 A C1 7 1 7 7 1 8 PI 5 16...
Page 324: ...RU 321 6 7 9 9 1 6 1 2 1 2 3 18 4 5...
Page 325: ...RU 322 9 2 DAB 19 9 3 DAB 20 19 3 4 5 6 18...
Page 331: ...RU 328 1 3 C 1 1 1 4 D E 9 3 F 10 3 10 2 1 2 3 4 5 1 E 2 5 26 24 25...
Page 332: ...RU 329 6 10 3 1 27 2 F 10 1 27 3 27 4 27 5 6 2 D F 27 7 27 27 1 2 3 4 5 6...
Page 336: ...RU 333 12 10 4 3 2 SP RP 6 7 8 9 1 2 3 1 1 2 3 1 2 1 2 10 3 1 2 SP RP 1 2...
Page 337: ...RU 334 BL 1 2 3 RM 1 2 3 RM BP1 1 1 OC 1 2 1 2 PB 1 2 1 2 13 14...
Page 340: ......
Page 394: ......
Page 448: ......
Page 501: ...ROM N RO 498...
Page 504: ......
Page 505: ...GR 502 IEC 364 CEI 64 2 1000 Kg m3 1mm2 s i e sybox e sybox 30 50 e sybox H...
Page 506: ...GR 503 1 6 1 2 2 3 1 2 3 4 5 6 10 3 C 4 4 2 1 OUT 2 3 A B C D E F 1 A B E F...
Page 513: ...GR 510 2 2 1 C 9 C OUT 9 D OUT2 9 2 1 GAS e 8 2 2 2 90 10 4 4 10...
Page 514: ...GR 511 2 2 3 3_ 5 F 1 1 5 1 5 11 x4 x4 F 1 3_ 5 3 8 bar 8 e sybox 7 e sybox 30 50 3 1...
Page 522: ...GR 519 Setpoint 2 5 5 5 2 2 7 8 1 2 6 1 MODE SET Setpoint MODE 7 ONOMA TOY MENOY 2...
Page 540: ...GR 537 F4 KIWA Ix Ix 10 F4 11 C F4 12 F4 8 C F3 9 7 6 15 5 KIWA 18 Ix 1 7 6 2 1 F4 F4 2 18 17...
Page 545: ...GR 542 9 2 DAP 19 9 3 DAB 19 6 O ring 7 18 3 4 5 6...
Page 551: ...GR 548 C 1 1 1 4 D 9 3 24 25 F 10 3 10 2 1 2 3 4 5 1 2 5 6 26...
Page 552: ...GR 549 10 3 1 27 2 F 10 1 27 3 27 4 27 5 6 2 O Ring D F 27 7 27 27 1 2 3 4 5 6...
Page 556: ...GR 553 10 4 3 2 SP RP 1 2 3 4 1 2 3 1 1 2 3 1 2 1 2 10 3 1 2 SP RP 1 2...
Page 557: ...GR 554 BL 1 2 3 setpoint RM 1 2 3 RM setpoint BP1 1 1 OC 1 2 1 2 PB 1 2 1 2 13 14...
Page 560: ......
Page 616: ......
Page 669: ...T RK E TR 666...
Page 672: ......
Page 728: ......
Page 781: ...ESKY CZ 778...
Page 784: ......
Page 838: ......
Page 839: ...BG 836 1000 1 e sybox e sybox 30 50 e sybox IEC 364...
Page 841: ...BG 838 1 1 4 4 5 SP 3 0 bar RP 0 3 bar 5 6 7 5 6 7 1 2 2 SP RP 6 7 3 1...
Page 846: ...BG 843 270 B 200 A 10 D 2 2 1 C IN 9 C OUT 1 9 D OUT 2 9 1 GAS 8 2 2 2 0 90 10 4 4 4 10...
Page 847: ...BG 844 2 2 3 F 1 1 5 1 5 F 3 3_ 5 11 x4 x4 3 8 8 e sybox 7 e sybox30 50 3 1 A...
Page 854: ...BG 851 5 5 wireless wireless 8 2 1 2 6 1 MODE SET MODE 7 2 2 5 5 5 2 2 7...
Page 856: ...BG 853 FF Log AY AE AF I1 1 I2 2 I3 3 I4 4 O1 1 O2 Funzione uscita 2 FW RF PW...
Page 858: ...BG 855 2 76 9 GO SB DIS F1 F3 F4 P1 1 P2 2 P3 3 P4 4 E EE EEprom 9 6 3 rpm psi kW 14...
Page 874: ...BG 871 1 2 1 2 3 O 18 4 5 t O 6 7 18 3 4 5 6...
Page 875: ...BG 872 9 2 DAB 19 9 3 DAB 19 20 9 4 9 4 1 wireless 4 r 9 4 2 20...
Page 881: ...BG 878 27 7 27 27 1 2 3 4 5 6 10 4 1 27 2 3 4 10 5 1 2...
Page 884: ...BG 881 1 2 3 1 1 2 3 1 2 1 2 10 3 1 2 12 off t off 10 4 3 2 SP RP 1 2 3 4...
Page 885: ...BG 882 13 14 SP RP 1 2 BL 1 2 3 RM 1 2 3 RM BP1 1 1 OC 1 2 1 2 PB 1 2 1 2...
Page 886: ...BG 883...
Page 889: ......
Page 890: ...887 1mm2 s kg m 1000...
Page 891: ...888 A 1 2 3 4 5 6 B 4 C 1 1 B C D E F B E F 3 2...
Page 892: ...889 IN OUT D C 4 E 2 F 1 1 bar 0 SP 3 bar 3 RP 0 5 6 7 1 2 2 5 4 4...
Page 897: ...894 270 B 200 A 10 D 2 2 1 OUT 1 IN C 9 OUT 2 D GAS 2 2 2 90 4 4 10...
Page 898: ...895 2 2 3 1 5 3 8 7 8 3 1 A 3 2 11 x4 x4...
Page 899: ...896 SP RP 10 1 2 7 3 0 0 3 27 3 3 10 10 5 1 8 5 5 T2 4 3 2 1 E18 E19 E20 E21 Reset 15 PD FA...
Page 906: ...903...
Page 907: ...904 AY FF AE I1 1 I2 2 I3 3 I4 4 O1 1 O2 2 FW RF Reset PW Password...
Page 923: ...920 1 2 3 4 5 6 7 18 3 4 5 6...
Page 924: ...921 2 9 3 9 19 4 9 1 4 9 4 1 2 3 2 4 9 3 4 9 20...
Page 928: ...925 2 3 B 2 C 24 D 25 E 26 F 2 10 1 2 23 24 25 26...
Page 929: ...926 3 4 5 6 3 10 1 F 2 3 4 5 6 7 27 1 2 3 4 5 6...