7.6.3 - T2: Delay in switching off
Sets the delay with which the inverter must switch off after switch-off con
-
ditions have been reached: plant under pressure and flow rate lower than
the minimum flow.
T2 can be set between 2 and 120 s. The factory setting is 10 s.
7.6.4 - GP: Proportional gain coefficient
Generally the proportional term must be increased for systems character
-
ised by elasticity (for example with PVC pipes) and lowered in rigid sys
-
tems (for example with iron pipes).
To keep the pressure in the system constant, the inverter performs a type
PI control on the measured pressure error. Depending on this error the
inverter calculates the power to be supplied to the motor. The behaviour
of this control depends on the set GP and GI parameters. To cope with
the different behaviour of the various types of hydraulic plants where the
system can work, the inverter allows the selection of parameters different
from those set by the factory. For nearly all plants the factory-set GP and
GI parameters are optimal. However, should any problems occur in ad
-
justment, these settings may be varied.
7.6.5 - GI: Integral gain coefficient
IIn the presence of large falls in pressure due to a sudden increase of the
flow or a slow response of the system, increase the value of GI. Instead,
if there are swings in pressure around the setpoint value, decrease the
value of GI.
7.6.6 - RM: Maximum speed
ISets a maximum limit on the number of pump revolutions.
7.6.7 - Setting the number of devices and of reserves
7.6.8 - NA: Active devices
Sets the maximum number of devices that participate in pumping.
It may have values between 1 and the number of devices present (max 4).
The default value for NA is N, that is the number of devices present in the
IMPORTANT:
To obtain satisfactory pressure adjustments, you gener
-
ally have to adjust both GP and GI
chain; this means that if devices are added to or removed from the chain,
NA always has the value of the number of devices present, automatically
detected. If a number different from N is set, this fixes the maximum num
-
ber of devices that can participate in pumping at the number set.
This parameter is used in cases where there is a limit on the pumps you
can or want to be able to keep running, and if you want to keep one or
more devices as a reserve (see 7.6.10 IC: Configuration of the reserve and
other examples below).
On the same menu page you can also see (but not change) the other two
system parameters linked to this, that is N, the number of devices present,
acquired automatically by the system, and NC, the maximum number of
simultaneous devices.
7.6.9 NC: Simultaneous devices
Sets the maximum number of devices that can work at the same time.
It may have values between 1 and NA. The default value of NC is NA, this
means that even if NA increases, NC will have the value NA. If a number
different from NA is set, this releases you from NA and fixes the maximum
number of simultaneous devices at the number set. This parameter is used
in cases where there is a limit on the pumps you can or want to be able
to keep running (see 7.6.10 IC: Configuration of the reserve and other
examples below).
On the same menu page you can also see (but not change) the other two
system parameters linked to this, that is N, the number of devices present,
read automatically by the system, and NA, the number of active devices.
7.6.10 IC: Configuration of the reserve
Configures the device as automatic or reserve. If set on auto (default) the
device participates in normal pumping, if configured as reserves, minimum
starting priority is associated with it, this means that the device with this
setting will always start last. If a number of active devices is set that is one
lower than the number of devices present and if one element is set as re
-
serve, the effect obtained is that, if there are no problems, the reserve de
-
vice does not participate in regular pumping; instead, if one of the devices
that participates in pumping develops a fault (maybe loss of power supply,
tripping of a protection, etc.), the reserve device will start.
Summary of Contents for E.sybox 50
Page 6: ......
Page 59: ...ITALIANO IT 56...
Page 62: ......
Page 116: ......
Page 172: ......
Page 228: ......
Page 284: ......
Page 285: ...RU 282 IEC 364 CEI 64 2 1000 3 1 2 e sybox e sybox 30 50 e sybox...
Page 286: ...RU 283 6 1 A 2 2 3 1 2 3 4 5 6 B 10 3 C 4 4 2 1 IN 2 3 1 A B C D E F A B E F 1...
Page 287: ...RU 284 OUT D 1 OUT C 4 4 1 2 F 1 2 2 3 IN C 2 4 5 4 4 5 4 5 5 1 1 SP 3 0 RP 0 3 5 6 7...
Page 291: ...RU 288 10 E 270 200 2 1 1 F IN 7 F OUT 7 1 GAS 1 3 1 BSP 25 8 2 1 2 30 25 mm 25 mm 8...
Page 293: ...RU 290 2 2 1 IN 9 OUT 9 D OUT 2 9 2 1 GAS 8 2 2 2 90 10 4 4 10...
Page 294: ...RU 291 2 2 3 3_ 5 F 1 1 5 11 x4 x4 1 5 F 1 3 _ 5 3 8 8 e sybox 7 e sybox30 50 3 1...
Page 301: ...RU 298 6 128x240 POWER COMM ALARM 12 6 MODE 1 SET 12 3 EEprom SET 6 SET MODE 5 5 6...
Page 302: ...RU 299 5 5 5 2 2 7 8 1 2 6 1 MODE SET MODE 7 2 2...
Page 304: ...RU 301 FF AY AE AF I1 1 I2 2 I3 3 I4 4 O1 1 O2 2 FW RF PW...
Page 305: ...RU 302 6 2 14 MODE 8 8 15 14 13...
Page 306: ...RU 303 2 298 9 GO SB DIS F1 F3 F4 P1 1 P2 2 P3 3 P4 4 EE EEprom 9 6 3 14...
Page 307: ...RU 304 GO SB 15 15 10 6 4 PW 6 5 RF PW 7 7 1 MODE MODE 7 1 1 7 1 2 RS 7 1 3 VP 7 1 4 VF...
Page 308: ...RU 305 7 1 9 11 SB F 8 F SB 7 1 10 2 11 7 1 5 PO PO 7 1 6 C1 A C1 7 1 7 7 1 8 PI 5 16...
Page 324: ...RU 321 6 7 9 9 1 6 1 2 1 2 3 18 4 5...
Page 325: ...RU 322 9 2 DAB 19 9 3 DAB 20 19 3 4 5 6 18...
Page 331: ...RU 328 1 3 C 1 1 1 4 D E 9 3 F 10 3 10 2 1 2 3 4 5 1 E 2 5 26 24 25...
Page 332: ...RU 329 6 10 3 1 27 2 F 10 1 27 3 27 4 27 5 6 2 D F 27 7 27 27 1 2 3 4 5 6...
Page 336: ...RU 333 12 10 4 3 2 SP RP 6 7 8 9 1 2 3 1 1 2 3 1 2 1 2 10 3 1 2 SP RP 1 2...
Page 337: ...RU 334 BL 1 2 3 RM 1 2 3 RM BP1 1 1 OC 1 2 1 2 PB 1 2 1 2 13 14...
Page 340: ......
Page 394: ......
Page 448: ......
Page 501: ...ROM N RO 498...
Page 504: ......
Page 505: ...GR 502 IEC 364 CEI 64 2 1000 Kg m3 1mm2 s i e sybox e sybox 30 50 e sybox H...
Page 506: ...GR 503 1 6 1 2 2 3 1 2 3 4 5 6 10 3 C 4 4 2 1 OUT 2 3 A B C D E F 1 A B E F...
Page 513: ...GR 510 2 2 1 C 9 C OUT 9 D OUT2 9 2 1 GAS e 8 2 2 2 90 10 4 4 10...
Page 514: ...GR 511 2 2 3 3_ 5 F 1 1 5 1 5 11 x4 x4 F 1 3_ 5 3 8 bar 8 e sybox 7 e sybox 30 50 3 1...
Page 522: ...GR 519 Setpoint 2 5 5 5 2 2 7 8 1 2 6 1 MODE SET Setpoint MODE 7 ONOMA TOY MENOY 2...
Page 540: ...GR 537 F4 KIWA Ix Ix 10 F4 11 C F4 12 F4 8 C F3 9 7 6 15 5 KIWA 18 Ix 1 7 6 2 1 F4 F4 2 18 17...
Page 545: ...GR 542 9 2 DAP 19 9 3 DAB 19 6 O ring 7 18 3 4 5 6...
Page 551: ...GR 548 C 1 1 1 4 D 9 3 24 25 F 10 3 10 2 1 2 3 4 5 1 2 5 6 26...
Page 552: ...GR 549 10 3 1 27 2 F 10 1 27 3 27 4 27 5 6 2 O Ring D F 27 7 27 27 1 2 3 4 5 6...
Page 556: ...GR 553 10 4 3 2 SP RP 1 2 3 4 1 2 3 1 1 2 3 1 2 1 2 10 3 1 2 SP RP 1 2...
Page 557: ...GR 554 BL 1 2 3 setpoint RM 1 2 3 RM setpoint BP1 1 1 OC 1 2 1 2 PB 1 2 1 2 13 14...
Page 560: ......
Page 616: ......
Page 669: ...T RK E TR 666...
Page 672: ......
Page 728: ......
Page 781: ...ESKY CZ 778...
Page 784: ......
Page 838: ......
Page 839: ...BG 836 1000 1 e sybox e sybox 30 50 e sybox IEC 364...
Page 841: ...BG 838 1 1 4 4 5 SP 3 0 bar RP 0 3 bar 5 6 7 5 6 7 1 2 2 SP RP 6 7 3 1...
Page 846: ...BG 843 270 B 200 A 10 D 2 2 1 C IN 9 C OUT 1 9 D OUT 2 9 1 GAS 8 2 2 2 0 90 10 4 4 4 10...
Page 847: ...BG 844 2 2 3 F 1 1 5 1 5 F 3 3_ 5 11 x4 x4 3 8 8 e sybox 7 e sybox30 50 3 1 A...
Page 854: ...BG 851 5 5 wireless wireless 8 2 1 2 6 1 MODE SET MODE 7 2 2 5 5 5 2 2 7...
Page 856: ...BG 853 FF Log AY AE AF I1 1 I2 2 I3 3 I4 4 O1 1 O2 Funzione uscita 2 FW RF PW...
Page 858: ...BG 855 2 76 9 GO SB DIS F1 F3 F4 P1 1 P2 2 P3 3 P4 4 E EE EEprom 9 6 3 rpm psi kW 14...
Page 874: ...BG 871 1 2 1 2 3 O 18 4 5 t O 6 7 18 3 4 5 6...
Page 875: ...BG 872 9 2 DAB 19 9 3 DAB 19 20 9 4 9 4 1 wireless 4 r 9 4 2 20...
Page 881: ...BG 878 27 7 27 27 1 2 3 4 5 6 10 4 1 27 2 3 4 10 5 1 2...
Page 884: ...BG 881 1 2 3 1 1 2 3 1 2 1 2 10 3 1 2 12 off t off 10 4 3 2 SP RP 1 2 3 4...
Page 885: ...BG 882 13 14 SP RP 1 2 BL 1 2 3 RM 1 2 3 RM BP1 1 1 OC 1 2 1 2 PB 1 2 1 2...
Page 886: ...BG 883...
Page 889: ......
Page 890: ...887 1mm2 s kg m 1000...
Page 891: ...888 A 1 2 3 4 5 6 B 4 C 1 1 B C D E F B E F 3 2...
Page 892: ...889 IN OUT D C 4 E 2 F 1 1 bar 0 SP 3 bar 3 RP 0 5 6 7 1 2 2 5 4 4...
Page 897: ...894 270 B 200 A 10 D 2 2 1 OUT 1 IN C 9 OUT 2 D GAS 2 2 2 90 4 4 10...
Page 898: ...895 2 2 3 1 5 3 8 7 8 3 1 A 3 2 11 x4 x4...
Page 899: ...896 SP RP 10 1 2 7 3 0 0 3 27 3 3 10 10 5 1 8 5 5 T2 4 3 2 1 E18 E19 E20 E21 Reset 15 PD FA...
Page 906: ...903...
Page 907: ...904 AY FF AE I1 1 I2 2 I3 3 I4 4 O1 1 O2 2 FW RF Reset PW Password...
Page 923: ...920 1 2 3 4 5 6 7 18 3 4 5 6...
Page 924: ...921 2 9 3 9 19 4 9 1 4 9 4 1 2 3 2 4 9 3 4 9 20...
Page 928: ...925 2 3 B 2 C 24 D 25 E 26 F 2 10 1 2 23 24 25 26...
Page 929: ...926 3 4 5 6 3 10 1 F 2 3 4 5 6 7 27 1 2 3 4 5 6...