Cleanness Requirements
Dust poses the top threat to the running of the equipment. The indoor dust falling on the equipment may be adhered by
the static electricity, causing bad contact of the metallic joint. Such electrostatic adherence may occur more easily when
the relative humidity is low, not only affecting the use life of the equipment, but also causing communication faults. The
following table shows the requirements for the dust content and granularity in the equipment room.
Substance
Concentration Limit (particles/m
3
)
Dust particles (diameter
≥
0.5
μ
m)
≤
3.5
×
10
6
Dust particles (diameter
≥
5
μ
m)
≤
3
×
10
4
The air filter of the RG-S8614/S8610/S8606 B must be cleaned regularly to ensure good ventilation and dust
prevention.
Apart from dust, the salt, acid and sulfide in the air in the equipment room must also meet strict requirements; as such
poisonous substances may accelerate the corrosion of the metal and the aging of some parts. The equipment room
should be protected from the intrusion of harmful gases (for example, sulfur dioxide, sulfured hydrogen, nitrogen dioxide,
and chlorine), whose requirements are listed in the following table.
Gas
Average (mg/m
3
)
Maximum (mg/m
3
)
SO
2
0.3
1.0
H
2
S
0.1
0.5
NO
2
0.5
1.
0
Cl
2
0.1
0.3
The
Average
refers to the average limit of harmful gas in one week. The
Maximum
value is the upper limit of the
harmful gas measured in one week for up to 30 minutes every day.
Dusting Cycle Suggestions:
1. Clean the air filters every three months.
2. Dust the air intakes and exhaust vents of all modules every three months.
3. Dust the modules every one or two years.
4. Dust the fan shelves yearly.
5. Dust the chassis, including the backboard, every one or two years.
If the device is in a poor dust prevention environment, please increase the dusting times.
Power Requirements
Model
Power Module
Input Voltage
RG-S8614/S8610/S8606
AC power module: RG-PA1200
90
–264 VAC, 47–63 Hz
AC power module: RG-PA1200E
90
–264 VAC, 47–63 Hz
AC power module: RG-PA1200I
90
–264 VAC, 47–63 Hz
AC power module: RG-PA1200
90
–264 VAC, 47–63 Hz
AC power module: RG-PA1200I
90
–264 VAC, 47–63 Hz
DC power module: RG-PD1200
-36 VDC
–72 VDC
DC power module: RG-PD1200
-36 VDC
–-72 VDC
RG- S8606 B
AC power module: RG-PA800IF
90
–264 VAC, 47–63 Hz
The RG-S8614/S8610/S8606/S8606 B provides 1+1 redundancy of power supply. You are recommended to use
multiple power supplies for the equipment to ensure its continuous and stable operation by avoiding the impact of
unexpected power failures on the equipment.
When the dual power supply is applied, the type of the power supply should be identical.
Summary of Contents for RG-S8606 B
Page 1: ...RG S8600 Series Switch Hardware Installation and Reference Guide V1 78 ...
Page 58: ...Figure 2 3 Moving the RG S8606 Switch Figure 2 4 Moving the RG S8606 B Switch ...
Page 62: ...Figure 2 6 Ventilation of RG S8614 ...
Page 63: ...Figure 2 7 Ventilation of RG S8610 Figure 2 8 Ventilation of RG S8606 ...
Page 76: ...Figure 3 8 Installing the Power Supply of the RG S8606 Switch ...
Page 92: ...Figure 3 34 Board Components of the RG S8610 Figure 3 35 Board Components of RG S8606 ...
Page 116: ......