background image

 

Rev. d                         01/1                         10

 

DMP052E

 

 

SET-POINT COMPENSATION 

The operation SET-POINT can be fixed or determined by a compensation slope according to the 
value given by the compensation sensor. 
Both A1 and D1 temperature loops can be temperature 
compensated (the SC sensor is necessary) or humidity 
compensated (SH sensor). It is necessary to set the 

Cth

 

parameter to state the temperature and humidity 
compensation.

 

Both A2 and D2 humidity loops can be 

temperature compensated only (the SC sensor is 
necessary). 
The compensation slope is a broken line touching two 
points and given by four values. 
Depending on the value given by the sensor, a set-point value shall be defined in a range between 
a minimum and a maximum. 
“Negative Compensation” means when the operating set-point increases while the compensation 
sensor value decreases. 
“Positive Compensation” means when operating set-point 
increases by the increasing of compensation sensor 
value. 
It is possible to set Negative and Positive Compensations 
both for temperature and humidity control loops. 
Each operation set-point value, both by temperature 
(heating and/or cooling) and by humidity 
(humidification/dehumidification) control loop can be 
associated to a relevant slope resulting by two values: 

 

- SET-POINT 1 corresponding to TEMPERATURE 1 
- SET-POINT 2 corresponding to TEMPERATURE 2 

 

If the Compensation Sensor is present and the Compensation of an Operating Mode is enabled, it 
is necessary to determine the four values of the curve. Such values become eight in case of 
Operating Mode A3, A4 and D3 because it is necessary to set compensation both for the heating 
and for the cooling loops. In the latter case, if compensation should be disabled for one of the two 
Loops only, it is necessary to set the minimum Set-point equal to the maximum value achieving a 
fixed operation Set-point. It is not possible to enable compensation in Operating Mode D4. 
 
While the A2 and D2 loops can be compensated through the SC temperature sensor, loops A1 and 
D1 may be temperature or humidity compensated. The selection is made under the Level II menu 
(label Cth).

 

For the temperature compensation the Compensation Sensor used is the one connected to 

SC 

input, if not differently specified (“SC sharing” see paragraph related to LinkBus). To enable 
Compensation first connect or share the Compensation Sensor. If compensation is enabled on any 
Operating Mode and the Compensation Sensor is not connected correctly to 

SC 

terminal or is not 

shared correctly with other devices, the Anomaly led 

@

 

lights up and the control Set-point 

becomes the value set for fixed point, i.e. without Compensation. 
For humidity compensation the possible absence of SH sensor does not generate any fault since 
its value can be 0. 
By humidity control loops, the possibility to compensate the set point depending on 

SC

 signal is 

used either to perform the remote setting of humidity set point through a potentiometer (see remote 
set page 14) or e.g. to compensate linearly minus the room humidity set according to the inner 
temperature of glass surface (anti-frost function in swimming pools or wet environments). 
In this case, the temperature sensor connected to 

SC

 must be located in the indoor part of the 

glass wall. 
For all compensation parameters settings see page 18 

Summary of Contents for W500H

Page 1: ...DMP052E User s manual W500H H4 W500HMB HMB4 Temperature and humidity controller CONTROLLI 16010 SANT OLCESE Genova Italy Tel 39 01073061 Fax 39 0107306870 871 E mail info controlli eu Web www control...

Page 2: ...17 PARAMETER CONFIGURATION MENU 18 Parameters Loop PA1 Mode A1 18 Parameters Loop PA1 Mode A2 19 Parameters Loop PA1 Mode A3 Mode A4 19 Parameters Loop Pd1 Mode D1 20 Parameters loop P d 1 Mode D2 20...

Page 3: ...e to connect up to 4 different devices with other devices of the same W digital series with the purpose to share the sensor and the operating mode The local bus also allows the W500H to be supervised...

Page 4: ...s Cancel and menu exit Parameter programming and confirmation Operating mode override Led description Ao1 Led associated to analogue output 1 it is on during data display Ao2 Led associated to analogu...

Page 5: ...ing set When the set point is achieved the output is zero If the control temperature goes above the SPF Cooling Set point plus BPF Cooling Proportional Band the relevant analogue output goes to 100 eq...

Page 6: ...of a device following the Operating Mode is required The status of one of the two digital inputs D i 1 or D i 2 if it is required a stop and or start delay of a device following the status of one or b...

Page 7: ...humidity set points and bPH humidity band The comparison between internal and external enthalpy must last for at least a time exceeding 15 min to avoid output hunting when the enthalpy values are almo...

Page 8: ...h S W changeover set through D i 2 contact input is required By D i 2 open contact the loop goes to enthalpy control with winter set point by closed contact the loop goes to enthalpy control with summ...

Page 9: ...onferring to the INTEGRAL action the task to cancel the remaining error The two 0 10 Vdc analogue outputs can be P or P I therefore the parameters to be set for each output will be SET POINT with fixe...

Page 10: ...nd D3 because it is necessary to set compensation both for the heating and for the cooling loops In the latter case if compensation should be disabled for one of the two Loops only it is necessary to...

Page 11: ...op A greater heat supply allows a better operation of the humidification device avoiding the risk of condensation and improving the plant efficiency If the Minimum limit is enabled it is necessary to...

Page 12: ...her mode i e Changeover from digital inputs with dry contact operates on all Loops whose function is enabled AE1 or AE2 with value On Such operation has a priority with respect to other changeovers fr...

Page 13: ...th clock and H model without clock In both models if parameter Abo OFF enabling by clock disabled the Loop is STOPPED if parameter Abo ON it follows the time schedules in HMB model and it is always in...

Page 14: ...RTC is not necessary for the others the 4 controllers can operate according to the same time schedule The equipment without the RS485 serial communication port W500T or W500H can be supervised if con...

Page 15: ...nd do not carry out star connections The default values of the Bus menu are i d L 1 and n d L 1 For LinkBus address setting and sensor selection see page 20 ENTHALPY COMPARISON WITH OUTDOOR HUMIDITY S...

Page 16: ...utdoor sensor on USE ON is enabled it is possible to perform compensation through a value sent by communication bus supervision Practically it is a virtual sensor which can be used instead of a physic...

Page 17: ...the level 1 until the corresponding label r t c is reached The label d 0 0 days d00 Monday appears by pushing the Set key Push the buttons Up or Down to set If the keys are not pushed for some second...

Page 18: ...rs Parameters Parameters Parameters Heating operating Set point read only if the compensation is ON Minimum Set point of Heating compensation Minimum Temperature Humidity of Heating Compensation S o C...

Page 19: ...sired values are modified push the Set or Esc keys to exit The Compensation Integral Limit parameters are visible if the relevant functions in the Operating Mode Programme menu 2nd Level are enabled P...

Page 20: ...nt Maximum Humidity Limit Proportional Band S H H b H H Visible only with Compensation ON coP parameter On Visible only with max humidity limit ON LLH parameter On Cooling temperature Set point S t F...

Page 21: ...rameter to be modified The parameter value blinks showing the edit status push the Up and Down keys to change values Once the desired values are modified push the Set or Esc keys to exit Parameters Lo...

Page 22: ...Up and Down keys to change values Once the desired values are modified push the Set or Esc keys to exit The compensation integral and limit parameters are visible if the relevant functions in the oper...

Page 23: ...inimum temperature of humidification compensation SoH Sc1 tc1 Maximum Set point of humidification compensation Maximum temperature of humidification compensation Humidification Proportional Band Sc2 t...

Page 24: ...m temperature of de humidification compensation Sod Sc3 tc3 Maximum Set point of de humidification compensation Maximum temperature of de humidification compensation De humidification Proportional Ban...

Page 25: ...fixed mode or time changeover Set Set Set Set Set Set Level 2 Push Set for 10 seconds Set Set time schedule and operating mode Set Set Set Set Set Setting Setting Setting Setting P A 1 P A 2 P d 1 P...

Page 26: ...DMP052E Set Set Set Set Push Set for 5 seconds until the label YES appears Push Set for 10 seconds until the device is reset the display blinks Set buS dEF SdE LdE n d L i d L i b S Set LinkBus and Mo...

Page 27: ...le only with 1 2 and 4 operating modes coP only if SC compensation sensor if present Operating mode selection Enable from time schedule if present or permanent enable P I control enable o P A b o i n...

Page 28: ...odified The parameter value blinks showing the edit status push the Up and Down keys to change values Once the desired values are modified push the Set or Esc keys to exit Visible only with 1 and 4 op...

Page 29: ...meter value blinks showing the edit status push the Up and Down keys to change values Once the desired values are modified push the Set or Esc keys to exit Operating mode selection Enable from time sc...

Page 30: ...Rev d 01 1 30 DMP052E MENU DIAGRAM...

Page 31: ...0 30 a 1200 Cooling integral time sec With integral action enabled bPF 4 0 0 a 25 Cooling Loop Proportional Band With ST 2 3 4 operating modes On Off controller Pd1 Default Range Description Availabil...

Page 32: ...ting mode bEi 4 0 0 a 25 Enthalpy prop band with upper inside enthalpy 3 operating mode bEE 2 0 0 a 25 Enthalpy prop band with upper outside enthalpy 3 operating mode LLA 10 0 a 100 Minimum opening li...

Page 33: ...to 2 Change over mode 3 NM RF FA If clock is present W500HMB model co 4 h 19 0 to 23 Change over time 4 0 23 If clock is present W500HMB model 0 0 to 59 Change over minutes 4 0 59 If clock is present...

Page 34: ...In Mode3 S on W off Changeover SEo OFF Other ON OFF control enable 4 Operating mode rS OFF Switch off delay enable 4 Operating mode rA OFF Switch on delay enable 4 Operating mode Special Functions Sen...

Page 35: ...5 detects a temperature lower than the set value the controller stops the fan and closes the outside air damper Obstructed filter the pressure switch 7 signals the presence of obstructed filter if the...

Page 36: ...mper Obstructed filter the pressure switch 7 signals the presence of obstructed filter if the differential pressure before and after the filter increases over the set value Possible variants Remote se...

Page 37: ...ature sensor 10 is lower than inside one 2 sensor and it is winter time the inside air will have priority giving the possibility of minimum opening Vice versa in summertime ModBus supervision is possi...

Page 38: ...on off action of humidifier 9 The outside dampers inlet and exhaust and the return air one are controlled by one analogue output only and by setting the correct direct reverse action of the relevant...

Page 39: ...cooling request due to limit loop de humidification is higher than that the temperature one the controller will give priority to the de humidification request the limit loop signal is prevailing by co...

Page 40: ...air sensor 13 It is possible a separate control of return air fan with switch on delay with respect to the supply air fan on R2 controller in order to avoid over loading in electric supply at AHU star...

Page 41: ...e temperature is lower than the outside one Limit action anti frost or max temperature on D i 1 digital input Fan start up with stroke end switch of inlet and air exhaust dampers 8 in order to avoid c...

Page 42: ...duced The humidity set point is compensated by sensor 1 placed on swimming pool glass walls and connected to SC input When inside temperature of the glass wall surface due to low outside temperature d...

Reviews: