Rev. d                         01/1                         17

 

DMP052E

 

 

FRONT PANEL AND DATA ACCESS MENU 

Using Front Panel, it is possible to access the Parameters 
managed by the device. The data access Menu is subdivided 
into three different levels: 

Level 0 

– Main data display 

Level 1 

– Access to parameter configuration menu 

Level 2 

– Access to the Operating modes programme menu 

 

Level 0 

is the one displayed by default. If no keys are 

pushed for some seconds this level is automatically re-
entered from the higher levels. 
At this Menu level it is possible to visualize on the FND display the temperature values of the 
connected sensors (also via LinkBus) and the values of analogue outputs Ao1 and Ao2 expressed 

as a percentage. Data display is achieved by pushing the buttons 

Up 

 

or 

Down 

; while Led 

signalling the displayed analogue input or output lights up. If an input is not present, it is not 
displayed. The digital input led 

D.i.1 

and 

D.i.2 

are on with closed contact, the 

Rel1 

and 

Rel2 

relay 

output leds are on if they are energized. Such leds are always visible at any menu level. The 

Mode, Ovr 

and anomaly 

@

 

LEDs have already been described in the respective chapters. 

To access 

Level 1, 

push the Set key. At this level it is possible to change the control Parameters of 

the two analogue outputs 

[

P A 1

] and [

P A 2

]

of the two Relay Digital outputs [

P d 1

] and  

[

 

P d 2

] and, for W500HMB controllers only, also the clock [

 

r t c

]. It is always necessary to set 

the clock at the first start-up or if the equipment has been powered off for over 30 hours. In order to 
set date and time, scroll the menu at the level 1 until the corresponding label [ 

r t c

] is reached. 

The label [

 

d 0 0

 

] (days, d00 = Monday) appears by pushing the 

Set 

key. Push the buttons 

Up 

or 

Down 

to set. If the keys are not pushed for some seconds or by pressing 

Se

t, the label [

 

h 0 0

(hours) and [

 

’ 0 0

 

] (minutes) appears: push the buttons 

Up 

and 

Down 

to set respectively hour 

and minutes. To confirm and save, push 

Se

t. If the keypad is not pushed or by pressing the 

Esc 

key once, the start value appears. 

 

P A 1

] label corresponds to the Parameters of Analogue output 

at 

Ao1 

terminal 

P A 2

] label corresponds to the Parameters of Analogue output 

at 

Ao2 

terminal 

P d 1

]

 

label corresponds to the Parameters of Digital output 

of 

Rel1 

relay 

P d 2

] label corresponds to the Parameters of Digital output 

of 

Rel2 

relay 

 
To modify a parameter, it is necessary to push 

Set 

after selecting

 

the corresponding Label; the 

parameter value blinks and can be modified by pushing the keys 

Up 

to increase or 

Down 

to 

decrease. Push 

Set 

or 

Esc 

to exit. For the complete control parameter navigation see the 

Parameter Configuration Menu 

scheme from page 18. 

 

By pushing the 

Set 

key for at least 10 seconds, 

Level 2 

appears. At this menu level, it is possible 

to set: 
- the Operating-Set decrease in Reduced mode 
- the operating modes of the two analogue outputs 

[

P A 1

], [

 

P A 2

] and of the two relay outputs 

[

P d 1

]

 

and 

[

 

P d 2

- the address parameters for communication 

b u S

]

, for sensor selection 

[

S E L

], for data load 

[

L d E

]

, to save 

[

S d E

], 

restore 

[

d E F

]

 and, for W500HMB devices only, also the time 

schedules for the automatic changeover of the weekly and daily Operating Mode 

P r o

].

 

 

For data navigation see 

Programme menu for operating mode and time schedules 

on page 21 

Note: the time schedules are present only on W500HMB. 

53.9 

Summary of Contents for W500H

Page 1: ...DMP052E User s manual W500H H4 W500HMB HMB4 Temperature and humidity controller CONTROLLI 16010 SANT OLCESE Genova Italy Tel 39 01073061 Fax 39 0107306870 871 E mail info controlli eu Web www control...

Page 2: ...17 PARAMETER CONFIGURATION MENU 18 Parameters Loop PA1 Mode A1 18 Parameters Loop PA1 Mode A2 19 Parameters Loop PA1 Mode A3 Mode A4 19 Parameters Loop Pd1 Mode D1 20 Parameters loop P d 1 Mode D2 20...

Page 3: ...e to connect up to 4 different devices with other devices of the same W digital series with the purpose to share the sensor and the operating mode The local bus also allows the W500H to be supervised...

Page 4: ...s Cancel and menu exit Parameter programming and confirmation Operating mode override Led description Ao1 Led associated to analogue output 1 it is on during data display Ao2 Led associated to analogu...

Page 5: ...ing set When the set point is achieved the output is zero If the control temperature goes above the SPF Cooling Set point plus BPF Cooling Proportional Band the relevant analogue output goes to 100 eq...

Page 6: ...of a device following the Operating Mode is required The status of one of the two digital inputs D i 1 or D i 2 if it is required a stop and or start delay of a device following the status of one or b...

Page 7: ...humidity set points and bPH humidity band The comparison between internal and external enthalpy must last for at least a time exceeding 15 min to avoid output hunting when the enthalpy values are almo...

Page 8: ...h S W changeover set through D i 2 contact input is required By D i 2 open contact the loop goes to enthalpy control with winter set point by closed contact the loop goes to enthalpy control with summ...

Page 9: ...onferring to the INTEGRAL action the task to cancel the remaining error The two 0 10 Vdc analogue outputs can be P or P I therefore the parameters to be set for each output will be SET POINT with fixe...

Page 10: ...nd D3 because it is necessary to set compensation both for the heating and for the cooling loops In the latter case if compensation should be disabled for one of the two Loops only it is necessary to...

Page 11: ...op A greater heat supply allows a better operation of the humidification device avoiding the risk of condensation and improving the plant efficiency If the Minimum limit is enabled it is necessary to...

Page 12: ...her mode i e Changeover from digital inputs with dry contact operates on all Loops whose function is enabled AE1 or AE2 with value On Such operation has a priority with respect to other changeovers fr...

Page 13: ...th clock and H model without clock In both models if parameter Abo OFF enabling by clock disabled the Loop is STOPPED if parameter Abo ON it follows the time schedules in HMB model and it is always in...

Page 14: ...RTC is not necessary for the others the 4 controllers can operate according to the same time schedule The equipment without the RS485 serial communication port W500T or W500H can be supervised if con...

Page 15: ...nd do not carry out star connections The default values of the Bus menu are i d L 1 and n d L 1 For LinkBus address setting and sensor selection see page 20 ENTHALPY COMPARISON WITH OUTDOOR HUMIDITY S...

Page 16: ...utdoor sensor on USE ON is enabled it is possible to perform compensation through a value sent by communication bus supervision Practically it is a virtual sensor which can be used instead of a physic...

Page 17: ...the level 1 until the corresponding label r t c is reached The label d 0 0 days d00 Monday appears by pushing the Set key Push the buttons Up or Down to set If the keys are not pushed for some second...

Page 18: ...rs Parameters Parameters Parameters Heating operating Set point read only if the compensation is ON Minimum Set point of Heating compensation Minimum Temperature Humidity of Heating Compensation S o C...

Page 19: ...sired values are modified push the Set or Esc keys to exit The Compensation Integral Limit parameters are visible if the relevant functions in the Operating Mode Programme menu 2nd Level are enabled P...

Page 20: ...nt Maximum Humidity Limit Proportional Band S H H b H H Visible only with Compensation ON coP parameter On Visible only with max humidity limit ON LLH parameter On Cooling temperature Set point S t F...

Page 21: ...rameter to be modified The parameter value blinks showing the edit status push the Up and Down keys to change values Once the desired values are modified push the Set or Esc keys to exit Parameters Lo...

Page 22: ...Up and Down keys to change values Once the desired values are modified push the Set or Esc keys to exit The compensation integral and limit parameters are visible if the relevant functions in the oper...

Page 23: ...inimum temperature of humidification compensation SoH Sc1 tc1 Maximum Set point of humidification compensation Maximum temperature of humidification compensation Humidification Proportional Band Sc2 t...

Page 24: ...m temperature of de humidification compensation Sod Sc3 tc3 Maximum Set point of de humidification compensation Maximum temperature of de humidification compensation De humidification Proportional Ban...

Page 25: ...fixed mode or time changeover Set Set Set Set Set Set Level 2 Push Set for 10 seconds Set Set time schedule and operating mode Set Set Set Set Set Setting Setting Setting Setting P A 1 P A 2 P d 1 P...

Page 26: ...DMP052E Set Set Set Set Push Set for 5 seconds until the label YES appears Push Set for 10 seconds until the device is reset the display blinks Set buS dEF SdE LdE n d L i d L i b S Set LinkBus and Mo...

Page 27: ...le only with 1 2 and 4 operating modes coP only if SC compensation sensor if present Operating mode selection Enable from time schedule if present or permanent enable P I control enable o P A b o i n...

Page 28: ...odified The parameter value blinks showing the edit status push the Up and Down keys to change values Once the desired values are modified push the Set or Esc keys to exit Visible only with 1 and 4 op...

Page 29: ...meter value blinks showing the edit status push the Up and Down keys to change values Once the desired values are modified push the Set or Esc keys to exit Operating mode selection Enable from time sc...

Page 30: ...Rev d 01 1 30 DMP052E MENU DIAGRAM...

Page 31: ...0 30 a 1200 Cooling integral time sec With integral action enabled bPF 4 0 0 a 25 Cooling Loop Proportional Band With ST 2 3 4 operating modes On Off controller Pd1 Default Range Description Availabil...

Page 32: ...ting mode bEi 4 0 0 a 25 Enthalpy prop band with upper inside enthalpy 3 operating mode bEE 2 0 0 a 25 Enthalpy prop band with upper outside enthalpy 3 operating mode LLA 10 0 a 100 Minimum opening li...

Page 33: ...to 2 Change over mode 3 NM RF FA If clock is present W500HMB model co 4 h 19 0 to 23 Change over time 4 0 23 If clock is present W500HMB model 0 0 to 59 Change over minutes 4 0 59 If clock is present...

Page 34: ...In Mode3 S on W off Changeover SEo OFF Other ON OFF control enable 4 Operating mode rS OFF Switch off delay enable 4 Operating mode rA OFF Switch on delay enable 4 Operating mode Special Functions Sen...

Page 35: ...5 detects a temperature lower than the set value the controller stops the fan and closes the outside air damper Obstructed filter the pressure switch 7 signals the presence of obstructed filter if the...

Page 36: ...mper Obstructed filter the pressure switch 7 signals the presence of obstructed filter if the differential pressure before and after the filter increases over the set value Possible variants Remote se...

Page 37: ...ature sensor 10 is lower than inside one 2 sensor and it is winter time the inside air will have priority giving the possibility of minimum opening Vice versa in summertime ModBus supervision is possi...

Page 38: ...on off action of humidifier 9 The outside dampers inlet and exhaust and the return air one are controlled by one analogue output only and by setting the correct direct reverse action of the relevant...

Page 39: ...cooling request due to limit loop de humidification is higher than that the temperature one the controller will give priority to the de humidification request the limit loop signal is prevailing by co...

Page 40: ...air sensor 13 It is possible a separate control of return air fan with switch on delay with respect to the supply air fan on R2 controller in order to avoid over loading in electric supply at AHU star...

Page 41: ...e temperature is lower than the outside one Limit action anti frost or max temperature on D i 1 digital input Fan start up with stroke end switch of inlet and air exhaust dampers 8 in order to avoid c...

Page 42: ...duced The humidity set point is compensated by sensor 1 placed on swimming pool glass walls and connected to SC input When inside temperature of the glass wall surface due to low outside temperature d...

Reviews: