FRONT PANEL AND DATA ACCESS MENU
Using Front Panel, it is possible to access the Parameters
managed by the device. The data access Menu is subdivided
into three different levels:
Level 0
– Main data display
Level 1
– Access to parameter configuration menu
Level 2
– Access to the Operating modes programme menu
Level 0
is the one displayed by default. If no keys are
pushed for some seconds this level is automatically re-
entered from the higher levels.
At this Menu level it is possible to visualize on the FND display the temperature values of the
connected sensors (also via LinkBus) and the values of analogue outputs Ao1 and Ao2 expressed
as a percentage. Data display is achieved by pushing the buttons
Up
or
Down
; while Led
signalling the displayed analogue input or output lights up. If an input is not present, it is not
displayed. The digital input led
D.i.1
and
D.i.2
are on with closed contact, the
Rel1
and
Rel2
relay
output leds are on if they are energized. Such leds are always visible at any menu level. The
Mode, Ovr
and anomaly
@
LEDs have already been described in the respective chapters.
To access
Level 1,
push the Set key. At this level it is possible to change the control Parameters of
the two analogue outputs
[
P A 1
] and [
P A 2
]
,
of the two Relay Digital outputs [
P d 1
] and
[
P d 2
] and, for W500HMB controllers only, also the clock [
r t c
]. It is always necessary to set
the clock at the first start-up or if the equipment has been powered off for over 30 hours. In order to
set date and time, scroll the menu at the level 1 until the corresponding label [
r t c
] is reached.
The label [
d 0 0
] (days, d00 = Monday) appears by pushing the
Set
key. Push the buttons
Up
or
Down
to set. If the keys are not pushed for some seconds or by pressing
Se
t, the label [
h 0 0
]
(hours) and [
’ 0 0
] (minutes) appears: push the buttons
Up
and
Down
to set respectively hour
and minutes. To confirm and save, push
Se
t. If the keypad is not pushed or by pressing the
Esc
key once, the start value appears.
[
P A 1
] label corresponds to the Parameters of Analogue output
1
at
Ao1
terminal
[
P A 2
] label corresponds to the Parameters of Analogue output
2
at
Ao2
terminal
[
P d 1
]
label corresponds to the Parameters of Digital output
1
of
Rel1
relay
[
P d 2
] label corresponds to the Parameters of Digital output
2
of
Rel2
relay
To modify a parameter, it is necessary to push
Set
after selecting
the corresponding Label; the
parameter value blinks and can be modified by pushing the keys
Up
to increase or
Down
to
decrease. Push
Set
or
Esc
to exit. For the complete control parameter navigation see the
Parameter Configuration Menu
scheme from page 18.
By pushing the
Set
key for at least 10 seconds,
Level 2
appears. At this menu level, it is possible
to set:
- the Operating-Set decrease in Reduced mode
- the operating modes of the two analogue outputs
[
P A 1
], [
P A 2
] and of the two relay outputs
[
P d 1
]
and
[
P d 2
]
- the address parameters for communication
[
b u S
]
, for sensor selection
[
S E L
], for data load
[
L d E
]
, to save
[
S d E
],
restore
[
d E F
]
and, for W500HMB devices only, also the time
schedules for the automatic changeover of the weekly and daily Operating Mode
[
P r o
].
For data navigation see
Programme menu for operating mode and time schedules
on page 21
Note: the time schedules are present only on W500HMB.