Rev. d 01/1 22
DMP052E
Parameters Loop
P A 2
- Mode A2
Push
Set
key to select the parameter to be modified. The parameter value blinks showing the edit
status: push the
Up
and
Down
keys to change values. Once the desired values are modified, push
the
Set
or
Esc
keys to exit.
Parameter Loop
P A 2
- Mode A4
The parameters menu of A4 analogue operating mode is the sum of A1 and A2 modes parameters
menus. This menu contains all parameters since it is intended to manage both humidification and
dehumidification control loop. Push
Set
key to select the parameter to be modified. The parameter
value blinks showing the edit status: push the
Up
and
Down
keys to change values. Once the
desired values are modified, push the
Set
or
Esc
keys to exit.
The compensation, integral and limit parameters are visible if the relevant functions in the
operating mode programme menu (2
nd
level) are enabled.
Push set key for 10 sec. to enter such menu.
De-humidification operating Set-point (read-only)
Minimum Set-point of the de-humidification compensation
Minimum Temperature of de-humidification compensation
S o d
S c 3
t c 3
Max Set-point of de-humidification compensation
Max temperature of de-humidification compensation
De-humidification proportional band
S c 4
t c 4
b P d
De-humidification integral time
t i d
Visible only with compensation On (coP parameter = On )
De-humidification Set-point
S t d
Visible only with compensation off (coP parameter = Off )
Visible only with integral On ( int parameter = On )