Rev. d 01/1 31
DMP052E
TEMPERATURE CONTROL PARAMETER TABLES (LEVEL 1)
Analogue
controller
PA1
Default Range
Description
Availability
SoC
--
Heat operating set
Always (visualisation only cannot be set)
SoF
--
Cool operating Set
Always (visualisation only cannot be set)
StC
21.0 -50 a 150 Heating Loop Set
With ST, without Compens., 1, 3 , 4 operating modes
Sc1
20.0 -50 a 150 Heating compensation minimum Set
With ST and SC, Comp.enabled.,1,3, 4 operating modes
c1
5.0 -50 a 150 Heating compensation minimum temperature
With ST and SC, Comp.enabled.,1,3, 4 operating modes
Sc2
35.0 -50 a 150 Heating compensation max Set
With ST and SC, Comp.enabled.,1,3, 4 operating modes
c2
10.0 -50 a 150 Heating compensation max temperature
With ST and SC, Comp.enabled.,1,3, 4 operating modes
tiC
480 30 a 1200 Heating integral time (sec)
With integral action enable
bPc
4.0 0 a 25
Heating Loop Proportional Band
With ST, 1, 3, 4 operating modes
SLH
50.0 0 a 100
Humidity minimum Limit Loop Set
With LLH enabled, 1, 3, 4 operating modes
SHH
50.0 0 a 100
Max Humidity Limit Loop Set
With LLH enabled, 1, 3, 4 operating modes
bLH
4.0 0 a 25
Humidity minimum limit proportional Band
With LLH enabled, 1, 3, 4 operating modes
bHH
4.0 0 a 25
Humidity max limit proportional Band
With LHH enabled, 2, 3, 4 operating modes
StF
23.0 -50 a 150 Cooling Loop Set
With ST, without Compens., 2, 3, 4 operating modes
Sc3
10.0 -50 a 150 Cooling compensation minimum Set
With ST and SC, Comp.enabled.,2, 3, 4 operat. modes
c3
10.0 -50 a 150 Cooling compensation minimum temperature
With ST and SC, Comp.enabled.,2, 3, 4 operat. modes
Sc4
30.0 -50 a 150 Cooling compensation max Set
With ST and SC, Comp.enabled.,2, 3, 4 operat. modes
c4
15.0 -50 a 150 Cooling compensation max temperature
With ST and SC, Comp.enabled.,2, 3, 4 operat. modes
tiF
480 30 a 1200 Cooling integral time (sec)
With integral action enabled
bPF
4.0 0 a 25
Cooling Loop Proportional Band
With ST, 2, 3, 4 operating modes
On/Off
controller
Pd1
Default Range
Description
Availability
SoC
--
Heating operating Set
Always (visualisation only, cannot be Set)
SoF
--
Cooling operating Set
Always (visualisation only, cannot be Set)
StC
21.0 -50 a 150 Heating ON/OFF Set
With ST, without Compens., 1 and 3 operating modes
Sc1
20.0 -50 a 150 Heating compensation minimum Set
With ST and SC, comp. enabled, 1 and 3 operat. modes
c1
5.0 -50 a 150 Heating compensation minimum temperature
With ST and SC, comp. enabled, 1 and 3 operat. modes
Sc2
35.0 -50 a 150 Heating compensation max Set
With ST and SC, comp. enabled, 1 and 3 operat. modes
c2
10.0 -50 a 150 Heating compensation max temperature
With ST and SC, comp. enabled, 1 and 3 operat. modes
bPc
4.0 0 a 25
Heating ON/OFF hysteresis
With ST, 1 and 3 operating modes
SLH
50.0 0 a 100
Humidity minimum ON/OFF limit Set
With LLL enabled, 1 and 3 operating modes
SHH
50.0 0 a 100
Humidity max ON/OFF limit Set
With LLH enabled, 2 and 3 operating modes
bLH
4.0 0 a 25
Humidity minimum ON/OFF limit hysteresis
With LLL enabled, 1 and 3 operating modes
bHH
4.0 0 a 25
Humidity max ON/OFF limit hysteresis
With LLH enabled, 1 and 3 operating modes
StF
24.0 -50 a 150 Cooling ON/OFF Set
With ST, without Compens.,2 and 3 operating modes
Sc3
8.0 -50 a 150 Cooling compensation minimum Set
With ST and SC, Comp. enabled., 2 and 3 oper. modes
c3
0.0 -50 a 150 Cooling compensation minimum temperature
With ST and SC, Comp. enabled., 2 and 3 oper. modes
Sc4
15.0 -50 a 150 Cooling compensation max Set
With ST and SC, Comp. enabled., 2 and 3 oper. modes
c4
40.0 -50 a 150 Cooling compensation max temperature
With ST and SC, Comp. enabled., 2 and 3 oper. modes
bPF
4.0 0 a 25
Cooling ON/OFF hysteresis
With ST, 2 and 3 operating modes
trS
0
0 a 1999 Switch- off delay time (sec)
4 operating mode
trA
0
0 a 1999 Switch- on delay time (sec)
4 operating mode