Rev. d 01/1 19
DMP052E
Parameters Loop
PA1
- Mode A2
Push
Set
key to select the parameter to be modified. The parameter value blinks showing the edit
status: push the
Up
and
Down
keys to change values. Once the desired values are modified, push
the
Set
or
Esc
keys to exit.
Parameters Loop
PA1
- Mode A3 / Mode A4
The parameter menu of the Analogue Operating Modes A3/A4 is the sum of A1/A2 Modes
parameter menus. This Menu contains all parameters, since these modes are intended to manage
both heating and cooling control loops.
Push
Set
key to select the parameter to be modified. The parameter value blinks showing the edit
status: push the
Up
and
Down
keys to change values. Once the desired values are modified, push
the
Set
or
Esc
keys to exit. The Compensation/Integral/Limit parameters are visible if the relevant
functions in the Operating Mode Programme menu (2
nd
Level) are enabled. Push
Set
key for 10
seconds to enter the menu.
Cooling operating Set-point (read-only)
Minimum Set-point of Cooling compensation
Minimum Temperature/Humidity of Cooling Compensation
S o F
S c 3
c 3
Max Set point of Cooling Compensation
Max Temperature/Humidity of Cooling Compensation
Cooling Proportional Band
S c 4
c 4
b P F
Cooling Integral time
t i F
Maximum Humidity Limit Set point
Maximum humidity limit Proportional band
S H F
b H F
Visible only with Compensation On ( coP = ON ) setting
)
Visible only with Integral ON (int parameter = On )
Visible only with Maximum limit ON (LLH parameter = On )
Cooling temperature Set-point
S t F
Visible only with Compensation Off ( coP = OFF ) setting