DMP052E
TABLES OF OPERATING MODES AND TIME SCHEDULES (LEVEL 2)
Time schedules: (Pro)
Weekly schedule
(Pr7)
Default Range
Description
Availability
d1 (MON)
3
0 to 5
Fixed mode or daily sched.(On, rid, OFF, Pr1-2-3
)
If clock is present (W500HMB model)
d2 (TUE)
3
0 to 5
Fixed mode or daily sched.(On, rid, OFF, Pr1-2-3)
If clock is present (W500HMB model)
d3 (WED)
3
0 to 5
Fixed mode or daily sched.(On, rid, OFF, Pr1-2-3)
If clock is present (W500HMB model)
d4 (THU)
3
0 to 5
Fixed mode or daily sched.(On, rid, OFF, Pr1-2-3)
If clock is present (W500HMB model)
d5 (FRI)
3
0 to 5
Fixed mode or daily sched.(On, rid, OFF, Pr1-2-3)
If clock is present (W500HMB model)
d6 (SAT)
1
0 to 5
Fixed mode or daily sched.(On, rid, OFF, Pr1-2-3)
If clock is present (W500HMB model)
d7 (SUN)
2
0 to 5
Fixed mode or daily sched.(On, rid, OFF, Pr1-2-3)
If clock is present (W500HMB model)
Daily schedule
(Prd)
Default Range
Description
Availability
co 1: h
7
0 to 23
Change-over time 1
If clock is present (W500HMB model)
: '
30
0 to 59
Change-over minutes 1
If clock is present (W500HMB model)
: r
0
0 to 2
Change-over mode 1 (NM, RF, FA)
If clock is present (W500HMB model)
co 2: h
12
0 to 23
Change-over time 2 (0-23)
If clock is present (W500HMB model)
: '
30
0 to 59
Change-over minutes 2 (0-59)
If clock is present (W500HMB model)
: r
1
0 to 2
Change-over mode 2 (NM, RF, FA)
If clock is present (W500HMB model)
co 3: h
13
0 to 23
Change-over time 3 (0-23)
If clock is present (W500HMB model)
: '
30
0 to 59
Change-over minutes 3 (0-59)
If clock is present (W500HMB model)
: r
0
0 to 2
Change-over mode 3 (NM, RF, FA)
If clock is present (W500HMB model)
co 4: h
19
0 to 23
Change-over time 4 (0-23)
If clock is present (W500HMB model)
: '
0
0 to 59
Change-over minutes 4 (0-59)
If clock is present (W500HMB model)
: r
2
0 to 2
Change-over mode 4 (NM, RF, FA)
If clock is present (W500HMB model)
Reduced Set
(rid)
Default Range
Description Availability
RiC
3
0 to 20
Heating Set decrease
Always
RiF
5
0 to 20
Cooling Set decrease
Always
RiH
5
0 to 20
Humidity Set decrease
Always
Operating modes
Analogue contr.
PA1
Default Range
Description
Availability
Op
1
1 to 4
Operating mode (1, 2, 3, 4)
Always
Abo
OFF
Automatic/Manual enable (Clock)
Always
Int
OFF
Integral action enable
Always
coP
OFF
Compensated set enable
With SC sensor
LLH
OFF
Min. humidity limit loop enable
With SH sensor, 1 and 4 operating modes
LHH
OFF
Max. humidity limit loop enable
With SH sensor, 1 and 4 operating modes
AE1
OFF
Loop stop on DI1 (External enable 1)
Always
AE2
OFF
Loop stop on DI2 (External enable 2)
1, 2 and 4 operating modes. 3 Mode: S/W (off)
Changeover
On/Off contr.
Pd1
Default Range
Description
Availability
Op
1
1 to 4
Operating mode (1, 2, 3, 4)
Always
Abo
OFF
Automatic/Manual enable (Clock)
Always
coP
OFF
Compensated Set enable
With SC, 1, 2 and 3 operating modes
LLH
OFF
Min. (Low) ON/OFF limit enable
With SH, 1, 2 and 3 operating modes
LHH
OFF
Max. (High) ON/OFF limit enable
With SH, 1, 2 and 3 operating modes
AE1
OFF
Loop stop on DI1 (External enable 1)
Always
AE2
OFF
Loop stop on DI2 (External enable 2)
1, 2 and 4 operating mode.
In Mode3: S(on)/W (off) Changeover
SEo
OFF
Other ON/OFF control enable
Operating mode 4
RS
OFF
Switch off delay enable
Operating mode 4
RA
OFF
Switch on delay enable
Operating mode 4