Dinverter
A
User Guide
Issue code: d2au9
48
B2
B2
B3
B3
B4
B4
Digital input F3
Digital input F4
Digital input F5
Function
Digital control signals
Voltage range
0V to +24V
Absolute maximum voltage range
–3V to +30V relative to 0V common
Sampling period
8ms (120Hz)
Switching thresholds when operating in negative logic (default)...
Inactive (logic high)
≥
11.1V, or
≥
21.2k
Ω
connected to 0V
Active (logic low)
≤
4.4V, or
≤
2.6k
Ω
connected to 0V
Input resistance
5.6k
Ω
pull-up resistor
Switching thresholds when operating in positive logic...
Active (logic high)
≥
11.1V
Inactive (logic low)
≤
4.4V
Input resistance
5.6k
Ω
pull-down resistor
B5
B5
C3
C3
Digital input/output F1
Digital input/output F2
Function of terminal B5
External-trip input
Function of terminal C3
LOCAL/REMOTE
Voltage range
0V to +24V
Absolute maximum voltage range
–3V to +30V relative to 0V common
Sampling period (minimum period of
momentary contact operation)
8ms (120Hz)
Switching thresholds when operating in negative logic (default)...
Inactive (logic high)
≥
11.1V, or
≥
21.2k
Ω
connected to 0V
Active (logic low)
≤
4.4V, or
≤
2.6k
Ω
connected to 0V
Input resistance
5.6k
Ω
pull-up resistor
Switching thresholds when operating in positive logic...
Active (logic high)
≥
11.1V
Inactive (logic low)
≤
4.4V
Input resistance
5.6k
Ω
pull-down resistor
C1
C1
0V common