Dinverter
A
User Guide
Issue code: d2au9
83
PWM switching frequency
0.41
PWM switching
frequency
RW
Txt 3 (0)
6 (1)
9 (2)
12 (3)
3
(0)
Motor parameters
0.42
Motor –
number of poles
RW
Txt 2P (0)
4P (1)
6P (2)
8P (3)
4P
(1)
0.43
Motor –
power factor
RW
Uni 0 ~ 1
0.85
0.44
Motor –
rated voltage
RW
Uni 0 ~ 100
% [
AC
supply
voltage]
100
0.45
Motor – rated
full-load slip
RW
Uni 0 ~ 250
RPM
0
0.46
Motor –
rated current
RW
Uni 0 ~ FLC
A
FLC
0.47
Motor –
rated frequency
RW
Uni 0 ~ ULF
Hz
50 (EUR)
60 (USA)
The values entered in these parameters should be obtained from the rating
plate on the motor. Refer to
Configuring
the Drive for the motor
in
Chapter 6.
[0.46] is the total current rating of the motor. The Drive derives the rated
torque-producing (real/active) component of the total motor current from:
[0.46]
×
[0.43]
Status
0.49
Security status
RO
Uni (See below)
Refer to
Identifying the security status
in Chapter 5.
0.50
Software version
RO
Uni 1.00 ~ 9.99
Software version 02.01.XX is displayed as
2.01