Fig. 14: Overview: End section
Fig. 15: Overview: Isometric view of the connection
(1)
Insulation profile
(4)
Connector
(2)
Difference in length between the insulation profile –
conductor bar approx. 15 mm
(5)
Connector cap
(3)
Clearance between 2 conductor bars,
2.5 mm + 1 mm per side
(6)
Conductor bar
4.4.1
Expansion
Since the individual conductor bars are solidly connected to each other, each pole is considered a continuous conductor bar.
The connector caps between the conductor bars are solidly connected to the conductor bars and move in line with the
conductor bars when they expand.
The insulation profiles of the conductor rail segments are 15 mm shorter than the conductor bar to compensate for the
differences in linear expansion between the insulation profile and conductor bar.
The end cap base is the anchor point for the conductor rail. The conductor rail must only be fitted with 1 end cap base at the
start of the conductor rail system. The start of the conductor rail system is defined as the end of the conductor rail with the
power feed.
The use of expansion elements is not planned in case of adherence to the maximum system length, permissible temperature
range, and installation specifications.
Provide free space of ≥ 200 mm, since the conductor rail system can expand.
connector
End of the rail system (without end cap bar)