Door operator
configuration
(check & set)
Check and Configure the parameters related to the
installed door operator (please refer to paragraph 5.1):
P05 SET
Car door locking device:
0 = not present,
1 = present
P22 CHECK Motor Closing rotation:
0 = clockwise
1 = counter-clockwise
P28 CHECK Skate type:
02 = S20
09 = S90
12 = S120
P90 CHECK Installed motor type:
00 = self-recognized
XX = manual selected motor type
P91 CHECK Self-recognized motor type:
00 = autoset procedure requested!?
XX = recognized motor type
P99 SET
MLC commands logic
0 = H active and RSC forced closing
1 = L active and RSC reduced speed
2 = H active and RSC reduced speed
3 = L active and RSC forced closing
4 = CAN BUS
Refer to paragraph
4.3.2 for the
information about
access to
Configuration Mode.
4
Inspection mode
Put CDD6 in inspection mode by pressing key
and
check the INSP. LED is ON.
INSP. LED is ON
5
Speed Profiles
check in Inspection
mode
Press continuously key
to execute the door closing
with normal speed, until the door is completely closed.
Press continuously key
to execute the door
opening with normal speed, until the door is completely
opened.
In case it is necessary to tune the speed profiles, please
refer to the paragraph 5.2.1
Display visualization:
“CL” blinking
“CL” fixed
“OP” blinking
“OP” fixed