Computec
CDD6
EN
CDD6: user manual – rev.07
Page 56/74
5.8.3
P-BA: Opening force limiter
This parameter allows to activate opening force limiter, that must be active according to EN81-20, at least
for the door made of glass.
Parameter value
Notes
00 = function disabled
The function is not enabled
01…99% = function
enabled
(
default value is 90%
)
The function is enabled, and the percentage represents the opening force limit set to
generate the reversing. In case the opening force limit is overpassed, the door drive
will react according to P-BB settings as described in the next table.
it is strongly recommended to measure with appropriate instrumentation to verify the code limit of
150N.
5.8.4
P-BB: Opening reversing type
This parameter allows to activate different reactions on the door drive, after an opening force limiter
detection.
Parameter value
Notes
00 = back-step
(
default value
)
In case the opening force limit is overpassed, the door drive will react as follows:
-
Stops immediately the door
-
Performs a back-step in the closing direction according to P-A3 mm
-
Waits for a time-out according to P-41 settings. During this time the
commands are ignored until the timeout is expired. After that the door drive
will execute the active command.
01 = no torque
In case the opening force limit is overpassed, the door drive will react as follows:
-
Stops immediately the door
-
Removes the torque to the motor, so the door can be moved manually
-
Waits for a time-out according to P-41 settings. During this time the
commands are ignored until the timeout is expired. After that the door drive
will execute the active command.