ECON-4 1.4.0 Global Guide
50
Setpoint group
Engine RPM
Related FW
1.4.0
configured ECON-4
extension module
Range [units]
BIN / DATA
Default value
DATA
Force value
NO
Step
-
Comm object
14363
Related applications
ALL
Setpoint visibility
Always
Description
CB Request value
CB position information source
BIN
Terminal S4.1 and S4.2
DATA
CAN bus
Note:
If possible, use binary control for CB request and wire terminal S4.1 and S4.2 to feedback signal.
This will assure fastest reaction of ECON4 when breaker is closed or opened. This is crucial to avoid
over speed in case of opening GCB under load for example.
CB request
Setpoint group
Main PID
Related FW
1.4.0
configured ECON-4
ADV extension module
Range [units]
Nominal RPM – Overspeed RPM
Default value
1750
Force value
NO
Step
1 RPM
Comm object
14408
Related applications
ALL
Setpoint visibility
WinScope only
Description
When actual RPM reaches this value Gas Dose (throttle position) is immediately set to Idle Fuel value or
zero (closed position) according setting in setpoint PreOverSpReduct .
PreOverSpeed