ECON-4 1.4.0 Global Guide
58
Setpoanticip
group
Main PID
Related FW
1.4.0
configured ECON-4 extension
module
Range [units]
0.0 - 100.0 [%]
Default value
0%
Force value
NO
Step
0.1 %
Comm object
11102
Related applications
ALL
Setpoanticip
visibility
WinScope only
Description
Governor is equipped by load anticipation feedback, which helps to keep stable speed in case of fast load
changes. In the case of load jump forces the ECON-4 governor output (Actuator lever) by jump according to
Load anticip setting.
Engine load value can be received via physical Analog input S3.2 ACTIVE POWER as 0 to 10V or 20 mA
signal (if setpoanticip Speed request=BIN or ANA) or via CAN bus in the case of communication to IS-NT
controller (if setpoanticip Speed request=DATA). In such case follow this configuration in GenConfig: /
I/O – Analog outputs – ECON-4 – AOUT1 = Gener values – Act.power rel.
In the configuration choose option Normalize – YES and resolution adjust to 0,1
There is 5 different setpoanticips
Load anticip
:
Load anticip 1
Load anticip 2
Load anticip 3
Load anticip 4
For more information about
Load anticip
setting please see
.
Load anticip