ECON-4 1.4.0 Global Guide
54
Setpoint group
Main PID
Related FW
1.4.0
configured ECON-4 extension
module
Range [units]
0.0 – 100.0 %
Default value
10%
Force value
NO
Step
0.1 %
Comm object
7177
Related applications
ALL
Setpoint visibility
Always
Description
Integration of the PID speed regulation loop..
Speed int
Note:
Setpoint is active for unloaded engine.
Setpoint group
Main PID
Related FW
1.4.0
configured ECON-4 extension
module
Range [units]
0.0 – 100.0 %
Default value
0%
Force value
NO
Step
0.1 %
Comm object
7178
Related applications
ALL
Setpoint visibility
Always
Description
Derivative part of the PID speed regulation loop.
Speed der
Note:
Setpoint is active for unloaded engine.