ECON-4 1.4.0 Global Guide
26
BO1 and 2 setting is separated and described in previous chapter
c. Configuration of Analogue inputs from IGS-NTto ECON-4 (those are signals from ECON4 to controller, in
our configuration it is named from controllers point of view, so inputs)
AIN1
– Engine RPM
The engine RPM can be sent from ECON-4 into the IS-NT via CAN line as well. Configure the AIN1 in the
following way:
Function – RPM pick-up
Sensor – Electronic
the IGS-NT controller.
d. Configuration of Analogue outputs from IGS-NT to ECON-4
AOUT1
– Active Power Rel
ECON-4 is equipped with the Load anticipation function to react as quickly as possible to the sudden
changes of the engine power. For this function ECON-4 needs information about power and in case of DATA
mode this can be sent to ECON-4 via CAN. Adjust the AOUT1 in the following way:
Source: Gener values: ActPwr rel
Normalize: YES
Resolution: 0,1
AOUT2
– Speed RequestThe Speed request in case of DATA mode is sent via CAN line. Configure the
output AOUT2 in the following way:
Source: Sync.