ECON-4 1.4.0 Global Guide
72
Setting is active when
Main PID
:
Actuator type = Act type 3
. Setpoint structure
for Woodward ITB 0-200 mA on page 69
.
8.1.9 Act type 4 – predefined for Heinzmann STG 10
There are 4 identical groups of setpoints in ECON-4. They are used to setup the output circuits for particular
types of actuators and tune the actuator position PID loop.
Note:
Normally these Actuator type setpoints are predefined from the factory and there is no need to readjust
them. Modify them if you have a non-standard, or non listed actuator only –
see List of tested actuators by
Setting is active when
Main PID
:
Actuator type = Act type 4
. Setpoint structure
for Woodward ITB 0-200 mA on page 69
.
8.1.10 Group: Analog sensors
Setpoint group
Analog sensors
Related FW
1.4.0
configured ECON-4 extension
module
Range [units]
Range: 0.0 – 100.0 %
Default value
0.0
Force value
NO
Step
0.1 %
Comm object
11125
Related applications
ALL
Setpoint visibility
WinScope only
Description
Value of analog input SPEED REQUEST for minimum possible speed reference (Nominal RPM-8%).
LoReqSpeed Inp
Note:
It is active only if the setpoint Speed request = ANA.
Setpoint group
Analog sensors
Related FW
1.4.0
configured ECON-4 extension
module
Range [units]
0.0 – 100.0 %
Default value
100 %
Force value
NO
Step
0.1 %
Comm object
11126
Related applications
ALL
Setpoint visibility
WinScope only
Description
Engine idle speed.
HiReqSpeed Inp
Note:
Input SPEED REQUEST active only if the setpoint Speed request = ANA.