ECON-4 1.4.0 Global Guide
65
Setpoint group
Main PID
Related FW
1.4.0
configured ECON-4
extension module
Range [units]
0.0 – 100.0 %
Default value
30%
Force value
NO
Step
0.1 %
Comm object
7191
Related applications
ALL
Setpoint visibility
Always
Description
Adjusts the actuator position in the Econ-4 Mode = MAN.
Act position
Setpoint group
Main PID
Related FW
1.4.0
configured ECON-4 extension
module
Range [units]
500 – 10 000 Hz
Default value
6000 Hz
Force value
NO
Step
1 Hz
Comm object
7194
Related applications
ALL
Setpoint visibility
Always
Description
Frequency of the PWM signal sent to ACT+ and ACT- outputs..
PWM rate
Note:
For Heinzmann actuators adjust the PWM rate to 6000 Hz. For Woodward PWM and current, GAC
actuators adjust the PWM rate to 2000Hz.
Setpoint group
Main PID
Related FW
1.4.0
configured ECON-4 extension
module
Range [units]
± 10 V
Default value
0.00 V
Force value
NO
Step
0.01 V
Comm object
14375
Related applications
ALL
Setpoint visibility
[[[Undefined variable Specific.WinScopeOnly]]]
Description
Together with Idle Fuel value creates coordinates for first point of Speed/Fuel line. For detailed description
see
see Speed governor function in parallel mode on page 38
.
SGO Bias
Note:
Setpoint is active for unloaded engine.