ECON-4 1.4.0 Global Guide
14
Binary inputs are used to control the function of the ECON-4 digital governor.
Binary inputs can be read from:
the physical Binary inputs (terminals S4.x),
from the CAN-bus (byte Command in the Receive PDO),
in dependence on the value of the setpoint Speed request.
Speed Request value
CB Request value
Input
BIN
ANA
DATA
BIN
DATA
MCB fdb
S4.1
Cmd.1
GCB fdb
S4.2
Cmd.2
NOMINAL
S4.3
S4.3
Cmd.2
SPEED UP
S4.4
X
X
SPEED DOWN
S4.5
X
X
RUN / STOP
S4.6
S4.6
S4.6 &
Cmd.3
DROOP
S4.7
S4.7
Cmd.4
RESERVE
S4.8
Note:
Cmd.x is bit x in the byte Command of the Receive PDO, see description of CAN protocol. S4.x
isECON-4 terminal. Both the physical Binary input S4.6 and the corresponding bit Cmd.3 received via
CANbus must be active to activate Binary input RUN in DATA mode. In case of lost communication on
CANbus, all bits of the byte Command are set to 0 – it deactivates
MCB fdb (S4.1)
Inputs GCB and MCB fdb decide which setpoints are used in PID speed regulation loop and which type of
regulation is used (Iddle/Island/Parallel):
MCB
state
GCB
state
lRPM - Requested RPMl > RPM window
PID constants
OFF
OFF
NO
Speed gain, Speed int, Speed der
OFF
OFF
YES
Speed gain, Speed int w, Speed der w
ON
OFF
NO
Speed gain, Speed int, Speed der
ON
OFF
YES
Speed gain, Speed int w, Speed der w
OFF
ON
-
Load gain, Load int, Load der
ON
ON
-
Load control according Speed/Fuel Line
Note:
There is more Load gain and Load der values in ECON-4 ADV. Which set will be used depends on actuall
power.
GCB fdb (S4.2)
Inputs GCB and MCB fdb decide which setpoints are used in PID speed regulation loop and which type of
regulation is used (Iddle/Island/Parallel):
MCB
state
GCB
state
lRPM - Requested RPMl > RPM window
PID constants
OFF
OFF
NO
Speed gain, Speed int, Speed der
OFF
OFF
YES
Speed gain, Speed int w, Speed der w
ON
OFF
NO
Speed gain, Speed int, Speed der