ECON-4 1.4.0 Global Guide
12
4.4 Recommended wiring
Postion
Terminal groups
Link
Power supply Actuators
Actuator feedback
Interface to actuators (page 18)
Analog inputs
Binary inputs
Magnetick Pick-up
Analog outputs
Communications
Communication wiring (page 20)
back to Installation and wiring
4.4.1 General
Use grounding terminals.
The “-“terminal of the battery has to be properly grounded.
Cables for binary inputs and analogue inputs must not be placed along power cables.
Analogue inputs should use shielded cables, especially when length >3m.
Always use shielded cable for Magnetic pick-up.