7 Technical data
Resolution
10 bits non electrically separated
Actuator feedback input
Number
2 non electrically separated
Resolution
10 bits
Range
0 - 10 V; input resistance 11 kΩ
0 - 20 mA; load resistor 50 Ω
Analog measurement
tolerance
1 %
Analog inputs
Number
1 non electrically separated
Resolution
0 - 100000
Range
0 - 10 V; output resistance < 1 kΩ
0 - 20 mA; Active current source
Analog measurement
tolerance
1 %
Analog outputs
Number
8
Input resistance
4.4 kΩ
Input range
0 - 36 V DC
Switching voltage level for close contact
indication
0 - 2 V
Max voltage level for open contact indication
8 - 36 V
Binary inputs
Maximal CAN bus length
200 m galvanically separated
Speed
250 kBd
Nominal impedance
120 Ω
Cable type
twisted pair (shielded)
CAN bus interface
Weight
600 g
Protection
IP20
General information
Operating temperature
- 30 to +70 ˚C
Storage temperature
-30 to +80˚C
Humidity
95% without condensation
Low voltage directive
EN 61010-1:95 +A1:97
Electromagnetic
compatibility
EN 50081-1:94, EN 50081-2:96
EN 50082-1:99, EN 50082-2:97
Vibrations
5 - 25 Hz, ± 1,6mm 25 - 100 Hz, a = 4 g
Shocks
a = 200 m/s
2
Operating conditions