ECON-4 1.4.0 Global Guide
53
Setpoint group
Engine RPM
Related FW
1.4.0
Range [units]
Start RPM - Nominal RPM
Default value
350 RPM
Force value
NO
Step
1 RPM
Comm object
7189
Related applications
ALL
Setpoint visibility
Always
Description
If ECON-4 detects speed higher then Starting RPM, it terminates the starting sequence end starts normal
speed regulation.
Starting RPM
Note:
ECON-4 can work only if Starting RPM < Idle RPM < Nominal RPM. If this condition is not met, ECON-4
activates bit Invalid setpoints in Transmit PDO 1, see description of CAN protocol. It is not possible to run the
engine if the bit Invalid setpoint is signalized.
8.1.5 Group: Main PIDGroup: ECON-4-MainPID
Setpoint group
Main PID
Related FW
1.4.0
configured ECON-4 extension
module
Range [units]
0.0 – 200.0 %
Default value
10%
Force value
NO
Step
0.1 %
Comm object
7176
Related applications
ALL
Setpoint visibility
Always
Description
Gain of the PID speed regulation loop.
Speed gain
Note:
Setpoint is active for unloaded engine.