Repair | 11
Operating instructions CMVpro 125-400 | Version 1-en
57 / 76
Fault
Possible cause
Fault discovery
Remedy
Winding damage on
the electric motor.
Winding measure-
ment.
Repair or replace elec-
tric motor
_
Electric motor bearing
damage.
Turn electric motor by
hand.
Damaged cable, faulty
cable connection.
Measurement, visual
inspection.
Replace cable.
Strong vibra-
tion.
Deposits on impeller,
imbalance.
Visual inspection, vi-
bration measurement.
Clean impeller
_
53].
Balance impeller
_
21].
Adjust cleaning inter-
val.
Damaged or mal-
formed impeller due to
(prohibited) conveyed
medium.
Visual inspection.
Replace impeller
_
Points to observe:
_
and
_
10].
Clarify composition of
conveyed medium and
plastic resistance.
Measure temperature
of the conveyed
medium.
Adjust operating con-
ditions to intended use
_
8].
Check operating point.
Check environmental
conditions.
Ductwork connected
directly to fan casing.
Adjust connection
(sleeve) and ductwork
distance appropriately
_
35].
Change in length of
ductwork due to ther-
mal expansion.
Loose impeller.
Can the impeller be
moved axially on the
motor shaft?
Adjust impeller posi-
tion
_
Clamp down clamping
adapter
_
Impeller dips into con-
densate at bottom of
casing.
Type K: visual inspec-
tion.
Drain condensate
_