Electrical Installation | 7
Operating instructions CMVpro 125-400 | Version 1-en
39 / 76
7
Electrical Installation
7.1
Safety instructions
These safety instructions warn against dangers that can arise during electrical
installation of the fan.
DANGER
Risk of injury due to electrical energy
Immediate danger to life due to respiratory and cardiac arrest.
▪ Erroneous or insufficient execution of the electrical connections, the wiring,
and the cable routing as well as the electrical safeguards of the fan.
u
Only authorized, qualified electricians may carry out the electrical installa-
tion and connect the fan to the power supply.
u
The electrical installation is to be executed in accordance with the standard
EN 60204-1, the technical connection requirements, and the relevant regu-
lations.
WARNING
Trip and fall hazard due to cables run along the floor
Bruises and other injuries.
u
Motor connection cables run along the floor are to be run properly and pro-
tected by a cover.
u
Indicate the trip hazard with floor markings.
WARNING
Risk of electrical shock due to electrostatic charge
Subsequent injuries due to response upon being startled.
▪ As a precaution, take protective measures against electrostatic charge
when operating the fan.
u
Ground the fan support.
u
For outside mounting, connect the fan support to the lightning protection
system.
CAUTION
Electrical hazards due to improper layout/undersizing of the
electric motor and protective devices.
Operation outside of the specified characteristic curves.
u
Size electrical protective devices according to the electric motor and con-
nection cables.
u
Operate only within the specified characteristic curves (flow rate and differ-
ential pressure) according to the technical data sheet.
7.2
Electrical protective devices
7.2.1
Isolation switch installation
Improper use of isolation switch
The isolation switch is only a protective device for disconnecting the fan from
electrical power during mounting, maintenance, or repair work and not to turn
the fan on and off in the context of operation.
The isolation switch
• is a required protective device,
• shall be installed in an easily-accessible location near the fan,