11 | Repair
62 / 76
Operating instructions CMVpro 125-400 | Version 1-en
1
2
3
• Loosen clamping adapter.
• Loosen and remove
fastening screw (1).
• Pull outer cone (2) from
the motor shaft with a
suitable release bolt (3)
(see detail).
• Remove impeller and
clamping adapter from mo-
tor shaft.
Fig. 36:
Removing impeller
The impeller is mounted directly to the motor shaft on fans CMVpro 125-200
with electric motors of size 100 or 112 as well as for CMVpro 250-400 with elec-
tric motors of size 132.
Mounting instructions
• For slip-free power transmission, the following shall be free of grease:
• Motor shaft.
• Impeller borehole.
• The outside of the clamping adapter borehole.
• Set impeller position
_
• Mount clamping adapter:
• Nest cones together such that the slots do not overlap.
• Tighten the fastening screws according to the table:
Fan/size
Fastener threads
Max. tightening torque
[Nm]
CMVpro 125
M4
6
CMVpro 160
M5
8
CMVpro 200
M6
15
CMVpro 250
M8
20
CMVpro 315
M10
20
CMVpro 400
M12
25
• Check impeller mobility.
NOTICE
The impeller may not grind.
• Heat new hub cap evenly to approx. 60 °C with hot air blower and press
onto hub.