Connecting Alarm Card Cables
Caution
Carefully adjust the cable in the cable-management brackets to prevent any kinks
or sharp bends in the interface cable. Kinks and sharp bends can destroy or
degrade the ability of the optical fiber to propagate the signal-encoded beam of
light accurately from one end of the cable to the other. Also, allow adequate strain
relief in the interface cable.
Step 6
Route the cable through the fingers on the vertical chassis cable-management
bracket and turn the latch on the front of the bracket to secure the cables in the
bracket.
Connecting Alarm Card Cables
Cisco 12006 and Cisco 12406 Routers have two alarm cards located in the two
slots immediately above the left power supply bay and directly below the clock
and scheduler card slots. Each alarm card is equipped with a standard DB-9
connector, labeled ALARM. This connector can be used to connect the router to
an external site alarm maintenance system so that any critical, major, and minor
alarms generated in the router also energize alarm relays on the alarm card and
activate the external site alarm.
Appendix A, “Technical Specifications,”
lists the
pin-to-signal correspondence between the connector pins and the alarm card relay
contacts.
Because alarm contact cables are entirely dependent on installation site
circumstances, alarm connector cables are not available from Cisco Systems.
Note
Only safety extra-low voltage (SELV) circuits can be connected to the alarm
connector. Maximum rating for the alarm circuit is 2A, 50VA.
Note
To comply with Telcordia GR-1089 NEBS standard for electromagnetic
compatibility and safety, you must use a shielded cable when connecting to the
external alarm ports on the alarm card. The shielded cable is terminated by
shielded connectors on both ends, with the cable shield material tied to both
connectors.