Spinner Always On (obsolete):
no longer functional, will be removed in future designs.
Zero velocity Overdrive
: allows Zero velocity to run slightly slower (neg.) or faster (pos) than truck speed.
Zero velocity Pulses Per Revolution
: Sensor signal pulses/rev. Default is 4.0
Zero velocity Impeller Diameter
: Unique value for a given Zero velocity system (inches).
Spinner Advanced Settings
Lock Strength
: Set at 0 and do not adjust.
Lock Increment:
SpreadSmart Rx PWM response increment. Set at 70 (no units). Increasing value causes spreader
to attempt to correct more frequently causing display to be more jumpy.
Update Laps
: Feedback adjustment response cycle rate. Allows coil to react. Set at 3 cycles. Increasing value makes
controller respond more slowly, decreasing makes controller respond more rapidly.
Unseat Drive Percent
: % of trim signal used to unseat valve at motion startup. Set at 50% typically.
Unseat Time
: Length of time that unseat signal is sent. Set at 10 (1 equals one
tenth of second).
Prewet Settings
Device Present
: select yes or no to tell the controller that an pre-wet pump is present.
Device Has Sensor
: select yes or no to tell the controller that a pre-wet sensor is present.
Minimum Trim PWM
: PWM value when Prewet pump starts pumping. Value determined at “trim” step.
Minimum Trim PPM
: Pulse per minute value received from flow sensor with Prewet system running at min. trim.
Maximum Trim PWM
: PWM value when pre-wet pump hits max output. Value determined at “trim”
Maximum
Trim PPM
: Pulse per minute value received from flow sensor when Prewet system is running at maximum trim.
Pulses Per Gallon
: Input value from the flow meter on the pre-wet system. Key conversion factor.
Pump Max. Gallon/Minute
: Input value from the pre-wet pump rating. Limit of open loop output.
Pre-Wet Advanced Settings
Lock Strength
: Set at 0 and do not adjust.
Lock Increment:
SpreadSmart Rx PWM response increment. Set at 70 (no units). Increasing value causes spreader
to attempt to correct more frequently causing display to be more jumpy.
Update Laps
: Feedback adjustment response cycle rate. Allows coil to react. Set at 3 cycles. Increasing value makes
controller respond more slowly, decreasing makes controller respond more rapidly.
Unseat Drive Percent
: % of trim signal used to unseat valve at startup. Set at 50% (To unseat sticky valves)
Unseat Time
: Length of time that unseat signal is sent. Set at 10 (1 equals 0.1 second).
Anti-Ice Settings:
Device Present
: select yes or no to tell the controller that an Anti-Ice pump is present.
Device Has Sensor
: select yes or no to tell the controller that an Anti-Ice sensor is present.
Minimum Trim PWM
: PWM value when anti-ice pump starts pumping. Value determined at “trim” step
Minimum
Trim PPM
: Pulse per minute value received from flow sensor when Anti-Ice system is running at minimum trim.
Maximum Trim PWM
: PWM value at anti-ice pump max output. Value determined at “trim” step.
Maximum Trim
PPM
: Pulse per minute value received from Anti-Ice liquid flow sensor when Anti-Ice system is running at max. trim.
Pulses Per Gallon
: Input value from the flow meter on the anti-ice system. Key conversion factor.
Pump Max. Gallon/Minute
: Input value from the anti-ice pump. Limit of open loop output.
Tier 1 Gallon/Minute
: Maximum flow rate of the Tier 1 booms (in gallons per minute)
Tier 2 Gallon/Minute
: Maximum flow rate of the Tier 2 booms (in gallons per minute).
Anti-Ice Advanced Settings
Lock Strength
: Set at 0 and do not adjust.
Lock Increment:
SpreadSmart Rx PWM response increment. Set at 70 (no units). Increasing value causes spreader
to attempt to correct more frequently causing display to be more jumpy.
Update Laps
: Feedback adjustment response cycle rate. Allows coil to react. Set at 3 cycles. Increasing value makes
controller respond more slowly, decreasing makes controller respond more rapidly.
Unseat Drive Percent
: % of trim signal used to unseat valve at motion startup. Set at 50% (to unseat sticky valves);
Unseat Time
: Length of time that unseat signal is sent. Set at 10 (1 equals one
tenth of second).
Speedometer Calibration – part of “Trim/Cal Menu”
Speedo Setting
: Pulses Per Mile traveled. Value determined during Speedo Trim step.