Installation :
The instrument is to be fit onto a DIN 46277 (EN 50022) rail . All connections
keep inside the cabinet.
Note that with the instrument powered on, the terminals could be dangerous to
touching and cover opening actions or elements removal may allow accessing
dangerous parts. Therefore, the instrument must not be used until this is completely
installed.
The instrument must be connected to a power supply circuit protected with gl
type (IEC 269 ) or M type fuses rated between 0.5 and 2 A. This circuit should be
provided with a circuit breaker or any equivalent element to connect or disconnect the
instrument from the power supply network. The supply and measuring voltage circuits
will be both connected through a wire with a minimum cross-section of 1 mm
2
.
The line of the current transformer secondary will have a minimum cross-
section of 2,5 mm
2
.