CVM-BDM supply network analyzer
-------- --- Page Nº 35
;
The
DELAY
set value is applied either to the connection or the
disconnection when the alarm conditions occur.
;
The programming units for the different parameters are:
Parameter
Format
Example
Voltage
Without decimals = V (xxxx)
With decimals = kV (xxx.x)
0220 = 220 V
25.30 = 25.30 kV
Current
A
0150 = 150 A
Powers
kW, kvar, kVA
0.540 = 540 W
250.5 = 250.5 kW
Energies
kW.h, kvar.h
Power factor
x.xx
- 0.7 = - 0.70
Frequency
xx.x
50.0 = 50 Hz
2
Connections of the RELAY OUTPUTS :
a.-
CVM-BDM-C2
( 2 relays ) :
Out1
Terminals
Signal
Out2
Terminals
Signal
RELAY1
27 - 26
N.O.
RELAY2
25- 24
N.O.
b.-
CVM-BDM-C420
( 1relay ) :
Out2
Terminals
Signal
RELAY1
25 - 24
N.O.
- Maximum voltage between terminals = 250 V a.c.