CVM-BDM supply network analyzer
-------- --- Page Nº 48
a.- Registers
assigned to different parameters measured by the
CVM-BDM
:
MODBUS REGISTERS
HEXA-DECIMAL
(longs)
PARAMETER
Units
PRESENT
Value
MAXIMUM
Value
MINIMUM
Value
Phase voltage - V 1
V x 10
00-01
100-101
200-201
Current - A 1
mA
02-03
102-103
202-203
Active power - kW1
W
04-05
104-105
204-205
inductive power-kvar L 1
var L
06-07
106-107
206-207
Capacitive power – kvarC 1
var C
08-09
108-109
208-209
Power factor - PF1
PF x 100
0A-0B
10A-10B
20A-20B
Phase voltage - V 2
V x 10
0C-0D
10C-10D
20C-20D
Current - A 2
mA
0E-0F
10E-10F
20E-20F
Active power - kW2
W
10-11
110-111
210-211
Inductive power-kvarL 2
var L
12-13
112-113
212-213
Capacitive power – kvarC 2
var C
14-15
114-115
214-215
Power factor - PF2
PF x 100
16-17
116-117
216-217
Phase voltage - V 3
V x 10
18-19
118-119
218-219
Current - A 3
mA
1A-1B
11A-11B
21A-21B
Active power - kW3
W
1C-1D
11C-11D
21C-21D
Inductive power– kvarL 3
var L
1E-1F
11E-11F
21E-21F
Capacitive power – kvarC 3
var C
20-21
120-121
220-221
Power factor - PF3
PF x 100
22-23
122-123
222-223
Phase voltage - V III
V x 10
24-25
124-125
224-225
Current - A III
mA
26-27
126-127
226-227
Three-phase active power - kW III
W
28-29
128-129
228-229
Three-phase inductive power– kvarL III
var
2A-2B
12A-12B
22A-22B
Three-phase capacitive power – kvarC III var
2C-2D
12C-12D
22C-22D
Three-phase power factor - PF III
PF x 100
2E-2F
12E-12F
22E-22F