12.- CVM-BDM... COMMUNICATIONS
----
One or some CVM-BDM... can be connected to a P.C.. With this system we
can get all the parameters in one central point of reading. The CVM-BDM..., has a
serial RS-485 type output. If we connect more than one device to the same
communication line, we have to assign to each of them a different code or direction
(from 01 to 255), since the P.C. needs the identification of every measuring point
12.1.- ! To take into account:
- PROTOCOL:
MODBUS © (
Question / Answer)
- CVM-BDM DEFAULT CONFIGURATION :
001 / 9.600 / 8 bits / N / 1 bit
- Available baud rates: 1.200 - 2.400 - 4.800 - 9.600 - 19.200 bauds
- RS-485 type output:
−
RS-485 connection will be carried out by means of a
twisted and
screened cable,
with a minimum of 3 wires, with a maximum
distance between the CVM-BDM and the last peripheral of 1.200 m.
The CVM-BDM uses a RS-485 communication bus allowing up to
a
maximum of 32 devices in parallel (Multi-point bus)
per port
used in the PC
.