CVM-BDM supply network analyzer
-------- --- Page Nº 51
EXAMPLE
QUESTION
0A 03 00 24 00 10 05 76
0A
CVMk number, 10 in decimal
03
Reading function
00 24
Starting address (first register )
00 10
Number of registers for reading
05 76
CRC character
ANSWER
0A 03 20 00 00 00 D4 00 00 23 28 00 00 0F A0 00 00 00
00 00 00 00 00 00 00 00 00 60 00 00 01 F4 00 00 0F A0
B7 8B
0A
CVM-BD number , 10 in decimal
03
Reading function ( 03 or 04 ).
20
Data response bytes
00 00 00 D4
Vav III (register 26 Hex) in decimal 212 V
00 00 23 28
mA av III in decimal 9000 mA
00 00 0F A0
W III in decimal 4000 W
00 00 00 00
varL III in decimal 0 varL
00 00 00 00
varC III in decimal 0 varC
00 00 00 60
PF in decimal 96 PF
00 00 01 F4
Hz in decimal 50 x 10 -> 50 Hz
00 00 0F A0
VA III in decimal 4000 mA
B7 B8
CRC character