CVM-BDM supply network analyzer
-------- --- Page Nº 49
MODBUS REGISTERS
HEXA-DECIMAL
(longs)
PARAMETER
Units
PRESENT
Value
MAXIMUM
Value
MINIMUM
Value
Frequency (L1) - Hz
Hz x 10
30-31
130-131
230-231
Three-phase apparent power kVA III
VA
32-33
132-133
232-233
Line-to-line voltage L1-L2 - V12
V x 10
34-35
134-135
234-235
Line-to-line voltage L2-L3 - V23
V x 10
36-37
136-137
236-237
Line-to-line voltage L3-L1 - V31
V x 10
38-39
138-139
238-239
Line-to-line voltage III
V x 10
3A-3B
13A-13B
23A-23B
Hours / minutes
3C-3D
Month / day
13C-13D
Minutes / seconds
23C-23D
Active energy (+) kW.h
W. h
3E-3F
Inductive reactive energy (+) kvar.h L
var.h L
40-41
Capacitive reactive energy (+) kvar.h C var.h C
42-43
Maximum power demand
Md (Pd)
44-45
144-145
244-245
Active energy (-) kW.h
W. h
46-47
Inductive reactive energy (-) kvar.h L
var.h L
48-49
Capacitive reactive energy (-) kvar.h C
var.h C
4A-4B
Neutral current
I
N
68-69
168-169
268-269
%THD V 1
% x 10
6A-6B
16A-16B
26A-26B
%THD V 2
% x 10
6C-6D
16C-16D
26C-26D
%THD V 3
% x 10
6E-6F
16E-16F
26E-26F
%THD I 1
% x 10
70-71
170-171
270-271
%THD I 2
% x 10
72-73
172-173
272-273
%THD I 3
% x 10
74-75
174-175
274-275
Date/Time *
2A94-2A95-2A96-2A97-2A98-2A99
* NOTE : DATE/TIME FORMAT
Register 2A94 2A95 2A96 2A97 2A98
2A99
Day
Month
Year
Hours
Minutes
Seconds