in which case the C/K value of the previous example would be
0.72
.
If the C/K is configured lower than the actual value, connections and disconnections
would occur continuously with few load variations (the system performs more opera-
tions than necessary).
If the C/K is configured higher, the regulator requires a higher demand for reactive
power in order to switch and perform fewer operations.
Press the
key to enter editing mode. It is identified by the
symbol and the blinking of the
digits to be modified.
The
key increases the digit value.
The
key decreases the digit value.
The
key skips to the previous digit and the
key skips to the next digit.
Press
to validate the data; the
symbol disappears from the display.
Minimum value:
0.02
Maximum value:
1.0
If the value entered is lower than the minimum value or higher than the maximum value, the backlight
of the display flashes and the value entered is replaced with the minimum or maximum value, or with
the last value validated.
Press the
key to access the next programming step.
If no keys are pressed for 5 minutes, the unit switches to the simulation screen,
.