Table 10 (Continuation):Alarm codes�
Code
Description
E09
(7)
Current x I THD Alarm
. The IxITHD levels in some of the phases are higher than those
configured in the IxITHD alarm. (IxITHD refers to the multiplication of the current by the
ITHD of the same current, see
"5.26.- CURRENT x I THD ALARM"
)
E10
(7)
Temperature Alarm
. The measured temperature is higher than that configured in the
Temperature alarm.
E11
No Connection Status
due to
E08
,
E09
or
E10
.
E12
Disconnection Status
due to
E08
,
E09
or
E10
.
E13
Leakage Alarm�
The leakage current is higher than that configured in the
Leakage Current
alarm.
E14
Repeated Leakage Alarm
. Leakages have been detected repeatedly in the system,
but they are not caused by a capacitor.
E15
Leakage in Capacitors Alarm
. Leakages have been detected, which were caused by
some of the capacitors, and this stage is disabled. The disabled capacitors will start to
blink on the screen. The
E13
message will also be displayed.
In order to enable these capacitors again, view the configuration of the Leakage alarm.
E16
Leakage transformer detection Alarm�
The Leakage alarm has been enabled, but the
unit does not detect the connection of the leakage current transformer.
E17
Number of connections alarm�
The configured number of operations has been ex-
ceeded (any capacitor)
(7)
In these alarms, two levels have been configured:
The
Lo
value:
When the unit exceeds this value for 30 minutes, the corresponding alarm
is triggered and, if alarm
E11
is enabled, the
Computer
SMART III FAST
unit enters
No
Connection
status and activates
alarm
E11
.
The
HI
value :
if the unit exceeds this value for 30 seconds, the corresponding alarm is
triggered and, if alarm
E12
is enabled, the
Computer SMART III FAST
unit enters
Disconnection
status and activates
alarm
E12
.
If the unit falls back under the
Lo
value for 10 minutes, it deactivates the alarms and returns to the
normal operating status.
In the
No Connection
status, the unit does not connect the stages, but also does not disconnect them
if the operation requires it.
In the
Disconnection
status, it disconnects the stages and does not allow them to connect.
40
Computer SMART III FAST
Instruction Manual
Summary of Contents for Computer SMART III FAST 12
Page 2: ...2 Computer SMART III FAST Instruction Manual...
Page 108: ...9 CE CERTIFICATE 108 Computer SMART III FAST Instruction Manual...
Page 109: ...109 Instruction Manual Computer SMART III FAST...
Page 110: ...110 Computer SMART III FAST Instruction Manual...
Page 111: ...111 Instruction Manual Computer SMART III FAST...