5�27�- TEMPERATURE ALARM
In this point the thresholds above which the temperature alarm (
E10
) is activated can be configured.
Note:
The alarm must be enabled
(
).
Press the
key to enter editing mode. It is identified by the
symbol and the blinking of the
digits to be modified.
The parameters to be configured are:
The
Lo
value :
when the unit exceeds this value for 30 minutes, alarm
E09
is triggered,
and if alarm
E11
is enabled
,
the
Computer SMART III FAST
unit enters
No Connection
status
and activates
alarm
E11
.
The
HI
value:
if the unit exceeds this value for 30 seconds, alarm
E09
is triggered, and if
alarm
E12
is enabled, the
Computer SMART III FAST
unit enters
Disconnection
status and
activates
alarm
E12
.
If the unit falls back under the
Lo
value for 10 minutes, it deactivates the alarms and returns to the
normal operating status.
In the
No Connection
status, the unit does not connect the stages, but also does not disconnect them
if the operation requires it.
In the
Disconnection
status, it disconnects all the stages and does not allow them to connect.
The
key increases the digit value.
The
key decreases the digit value.
The
key skips to the previous digit and the
key skips to the next digit.
Press
to validate the data; the
symbol disappears from the display.
Lo
Value
and
HI
Value:
Maximum value:
80ºC.
Minimum value:
0ºC
100
Computer SMART III FAST
Instruction Manual
Summary of Contents for Computer SMART III FAST 12
Page 2: ...2 Computer SMART III FAST Instruction Manual...
Page 108: ...9 CE CERTIFICATE 108 Computer SMART III FAST Instruction Manual...
Page 109: ...109 Instruction Manual Computer SMART III FAST...
Page 110: ...110 Computer SMART III FAST Instruction Manual...
Page 111: ...111 Instruction Manual Computer SMART III FAST...