5�2�- CURRENT TRANSFORMATION RATIO
The primary and secondary value of the current transformer is configured in this point.
Press the
key to enter editing mode. It is identified by the
symbol and the blinking of the
digits to be modified.
The
key increases the digit value or shows the next option.
The
key decreases the digit value or shows the next option.
The
key skips to the previous digit and the
key skips to the next digit.
Press
to validate the data; the
symbol disappears from the display.
Current primary:
Maximum
value:
9999.
Minimum
value:
1.
Current secondary:
Possible
values:
1 or
5.
Maximum possible current ratio:
2500.
Note:
T
he current ratio is the ratio between the current primary and secondary.
Maximum value of the current ratio x the voltage ratio:
200000.
If the value entered is lower than the minimum value or higher than the maximum value, the backlight
of the display flashes and the value entered is replaced with the minimum or maximum value, or with
the last value validated.
Press the
key to access the next programming step
If no keys are pressed for 5 minutes, the unit switches to the simulation screen,
.
72
Computer SMART III FAST
Instruction Manual
Summary of Contents for Computer SMART III FAST 12
Page 2: ...2 Computer SMART III FAST Instruction Manual...
Page 108: ...9 CE CERTIFICATE 108 Computer SMART III FAST Instruction Manual...
Page 109: ...109 Instruction Manual Computer SMART III FAST...
Page 110: ...110 Computer SMART III FAST Instruction Manual...
Page 111: ...111 Instruction Manual Computer SMART III FAST...