B
.-
Programming variables
The following functions are implemented for these variables:
Function 04
: reading logs.
Function 10
: Writing multiple logs.
Table 16:Modbus memory map: programming variables (Table 1)
Unit parameters
Configuration variable
Address
Serial number
(9)
1000-1003
Frame number
(9)
1010-1013
Version
(9)
1020-1021
Hardware log
(9)
1030-1033
(9)
The parameters of the unit have only implemented
function 04
.
Table 17:Modbus memory map: programming variables (Table 2)
RS-485 Communications
Configuration variable
Address
Valid data margin
Default value
Peripheral no.
1071
1 to 254
1
Speed
1072
0 (9600), 1 (19200)
1
Parity
1073
0 (none), 1 (odd), 2 (even)
0
Length
1074
0 (8 bits), 1 (7 bits)
0
Stop bits
1075
0 (1 bits), 1 (2 bits)
0
Table 18:Modbus memory map: programming variables (Table 3)
CPC-NET communications
Configuration variable
Address
Valid data margin
Default value
Speed
1082
0 (9600), 1(19200), 2(38400)
2
Parity
1083
0 (none), 1 (odd), 2 (even)
0
Stop bits
1085
0 (1 bits), 1 (2 bits)
0
Table 19:Modbus memory map: programming variables (Table 4)
Transformation ratios
Configuration variable
Address
Valid data margin
Default value
Current primary
1090
1 - 10000
5
Current secondary
1091
0 (1 A), 1 (5 A)
1
Voltage primary
1095-1096
1 -99999
400
Voltage secondary
1097-1098
1 -99999
400
Table 20:Modbus memory map: programming variables (Table 5)
Connection type
Configuration variable
Address
Valid data margin
Default value
Connection type
1100
0 (3U.3C), 1 (3U.1C), 2 (2U.1C)
0
Phase
(10)
1101
1
Current 1
(10) (11)
1102
1 (Phase 1 direct), 2 (Phase 2 direct),
3 (Phase 3 direct), 4 (Phase 1 reverse),
5 (Phase 2 reverse), 6 (Phase 3 reverse),
1
Current 2
(1)(11)
1103
2
Current 3
(1)(11)
1104
3
(10)
Only used when the connection type is other than 3U.3C.
(11)
Indicates the relationship between the assigned voltage and the current direction.
Example:
If you see Current 1 = 1, Current 2 = 5 and Current 3 = 3, this means that:
Current 1 is assigned to voltage 1 in the direct direction, current 2 is assigned to voltage 2 in the reverse direction
61
Instruction Manual
Computer SMART III FAST
Summary of Contents for Computer SMART III FAST 12
Page 2: ...2 Computer SMART III FAST Instruction Manual...
Page 108: ...9 CE CERTIFICATE 108 Computer SMART III FAST Instruction Manual...
Page 109: ...109 Instruction Manual Computer SMART III FAST...
Page 110: ...110 Computer SMART III FAST Instruction Manual...
Page 111: ...111 Instruction Manual Computer SMART III FAST...