5�17�- UNDERVOLTAGE TRIP
At this point we configure the voltage threshold over which the undervoltage trip function acts. This
function disables all the steps enabled in the event of any measured phase-phase voltages presenting
a value below the configured threshold. It will not enable them again until the measured phase-phase
voltages do not exceed the threshold.
Press the
key to enter edit mode. It is identified by the
symbol and the flashing of the
digits to be modified.
The voltage threshold is programmed as a percentage of the configured primary voltage’s value (“
”).
The
key increases the digit value or shows the next option.
The
key reduces the digit value or shows the next option.
The
key skips to the previous parameter and the
key skips to the next parameter.
Press
to validate the data; the
symbol disappears from the display.
Maximum value:
0 %.
Minimum value:
100 %.
Note:
If 0% is programmed, the functionality is disabled.
Note
:
The value displayed in the fourth row (0 in the image) is not editable and indicates the
number of times that the Undervoltage trip function has been activated. This value is reset each
time the value is reconfigured.
Press the
key to access the next programming step.
If no keys are pressed for 5 minutes, the device switches to the simulation screen,
.
89
Instruction Manual
Computer SMART III FAST
Summary of Contents for Computer SMART III FAST 12
Page 2: ...2 Computer SMART III FAST Instruction Manual...
Page 108: ...9 CE CERTIFICATE 108 Computer SMART III FAST Instruction Manual...
Page 109: ...109 Instruction Manual Computer SMART III FAST...
Page 110: ...110 Computer SMART III FAST Instruction Manual...
Page 111: ...111 Instruction Manual Computer SMART III FAST...