54
5.4.3
The analogue datapoints
Type
Index
NV name
SNVT Direction
Description
ANL
1
nvo_custom_1
113
output
Supply air filter CF1 fouling level
ANL
2
nvo_custom_2
113
output
Supply air duct pressure
ANL
3
nvo_custom_3
113
output
Return air filter CF1 fouling level
ANL
5
nvo_custom_5
113
output
Heat exchanger fouling
ANL
8
nvo_custom_8
161
output
Supply air fan flow rate
ANL
9
nvo_custom_9
161
output
Return air fan flow rate
ANL
16
nvo_custom_16
105
output
Room or return air temperature
ANL
17
nvo_custom_17
105
output
Supply air temperature
ANL
18
nvo_custom_18
105
output
Fresh air temperature
ANL
19
nvo_custom_19
105
output
Network water temperature
ANL
25
nvo_sortie_ana_1
9
output
Coil No.1 capacity
ANL
26
nvo_sortie_ana_2
9
output
Coil No.2 capacity
ANL
27
nvo_sortie_ana_3
9
output
Supply air variable drive
ANL
28
nvo_sortie_ana_4
9
output
Return air variable drive
ANL
37
nvo_etat_unite
9
output
Unit operating state:
Value 0
off
Value 1
opening of damper
Value 2
on
Value 3
switched on after a power failure
Value 4
standby
Value 5
switched off by a fault
Value 6
switched off by CMS
Value 7
post ventilation
ANL
44
nvi_T_regul
105
input
Comfort regulated temperature setpoint in "Precision"
mode (return or ambient)
ANL
44
nvo_T_regul
105
output
Comfort regulated temperature setpoint return in mode
"Precision" mode (return or ambient)
ANL
48
nvi_D_regul
161
input
Comfort supply air fan flow rate setpoint
ANL
48
nvo_D_regul
161
output
Comfort supply air fan flow rate setpoint return
ANL
49
nvi_P_regul
113
input
Comfort duct pressure setpoint
ANL
49
nvo_P_regul
113
output
Comfort duct pressure setpoint return