background image

Air handler configuration

These  air  handler  units  are  ready  to  install  in  any  position  shown  in

Figure 3

. Some XAH model coils require a section of duct between the

indoor coil and the modular air handler. See 

Horizontal right applications

.

 

H

orizontal right applications

An pan extension to reduce the risk of condensate blow-off is provided

with certain models of XAH indoor coils. It is essential to construct, insu

-

late, and attach a 6 in. length duct extension between the XAH coil cas

-

ing and the modular air handler casing to allow enough room to install

the pan extension. The suggested method is as follows:

Note: 

This method consists of two identical field fabricated duct sections.

1. Attach one duct section to the leaving air end of the XAH indoor coil.
2. Attach the other duct section to the entering air end of the modular

air handler.

3. Attach the two sections together using s-lock and drive cleats. See

Figure 4

.

 Note: 

A = modular air handler width (see column B in 

Table 1

)

Air handler and coil upflow, downflow, and horizontal posi

-

tions where not using a pan extension 

1.

Apply the neoprene gasket to the return air end of the air handler.

2.

Attach three tie plates to the external sides and back of the air han

-

dler casing using screws.

3.

Position  the  air  handler  casing  over  the  appropriate  coil  opening

(depending on configuration). See 

Figure 3

.

4.

Attach the three tie plates to the coil casing using screws.

5.

Remove the coil access panel.

6.

Slide the coil out of the coil cabinet and set the coil to the side.

7.

Locate the 2 in. wide foam gasket.

8.

Apply the foam gasket over the air handler and coil mating seams

on the interior of both unit sides and back.

9. Slide the coil into the housing and install the coil access panel and

coil filter door.Horizontal suspension

Horizontal suspension

It  is  possible  to  suspend  these  air  handlers  in  horizontal  applications.

Use  angle  steel support brackets  with minimum  3/8  in.  threaded  rods,

supporting  the  unit  from  the  bottom.  Attach  the  threaded  rods  at  the

locations  shown  in 

Figure  5

  or 

Figure  6

,  leaving  enough  clearance

between the door and the rod so that doors can be removed for service.

Figure 3:  

Typical installation

 Figure 4:  

Duct section - modular air handler - horizontal right

A1711-001

Upflow

Downflow

Horizontal right

Horizontal left

A

A1762-001

3.5 in.

1 in. flange in

1 in. duct liner

S-lock

Drive cleat

20.5 in.

 CAUTION

Do not lift the air handler by the cabinet brace. The cabinet brace is

held in place  by the coil  channel. The cabinet brace  could become

disengaged from the cabinet causing the air handler to fall, potentially

causing injury or damaging property. Refer to 

Figure 1

 in the 

Installa

-

tion Manual

 for the location of the cabinet braces.

NOTICE

When assembling the support structure, size to provide clearance for

access door removal. 

Figure 5:  

Suspension support locations for horizontal applications that 

do not require the drain pan extension

 Figure 6:  

Suspension support locations for horizontal applications that 

require the drain pan extension

!

A1771-001

21 3/4 in.

1 1/2 in.

1 in.

Minimum 3/8 in. threaded rod

Minimum 1 1/2 in. x 1 1/2 in.
(Angle recommended length 26 
in. minimum with 2 in. clearance 
on both sides of the air handler)

1 in.

1 1/2 in.

21 3/4 in.

Minimum 3/8 in. threaded rod

Minimum 1 1/2 in. x 1 1/2 in.
(Angle recommended length 26 
in. minimum with 2 in. clearance 
on both sides of the air handler)

A1769-001

28 3/4 in.

1 1/2 in.

1 in.

Minimum 3/8 in. 
threaded rod

Minimum 
1 1/2 in. x 1 1/2 in.
(Angle recommended 
length 26 in. minimum with 
2 in. clearance on both 
sides of the air handler)

This document does not replace the Installation Manual

,

 which must be referred to for detailed information.

Notes: 

1. The controls may require correct polarity on the power supply and a adequate ground.

2. These units are rated for use with single and three phase 208 V or 230 V supply power.

3. Use flexible duct connectors.

4. Supply air ductwork must remain the size of the supply opening for the first 12 in. before transition to the correct duct size.

5. The return and supply duct may be fastened to the bottom or sides of the air handler using screws no longer than 1/2 in..

6. Line voltage electrical knockouts are available on the left top and left casing side. Refer to the 

Installation Manual

 for information on correct sizing

of overcurrent protection and supply wire sizes.

7. Low voltage electrical knockouts are available on the right top and right casing side.

8. Seal electrical openings and duct connections to prevent air infiltration. 

9. If installing the air handler above a finished ceiling, use a secondary drain pan.

10. It is necessary to trap condensate drain pans and slope them toward the drain.

11. At start up, measure the external duct static and adjust the blower speed accordingly.

A1712-001

B

20 1/2 in.

21 1/2 in.

F

A

D

12 3/16 in.

19 1/8 in.

C

E

Bottom inlet 
dimensions

Service 
disconnect panel

Top outlet
dimensions

Figure 1:  

Dimensions

Table 1: 

Dimensions

1

Models

Dimensions

Wiring knockouts

2

A

B

C

D

E

F

Height (in.)

Width (in.)

Opening widths (in.)

Power (in.)

Control (in.)

JMET08BS2N1

22 3/4

17 1/2

16 1/2

16 1/2

7/8 (1/2)

1 3/8 (1)

1 23/32 (1 1/4)

7/8 (1/2)

JMET12BS2N1

22 3/4

17 1/2

16 1/2

16 1/2

JMET12CS2N1

22 3/4

21

20

20

JMET16CS2N1

22 3/4

21

20

20

JMET18DS2N1

22 3/4

24 1/2

23 1/2

23 1/2

1. All dimensions are in inches.

2. Actual size (conduit size)

Subject to change without notice. Published in U.S.A.

6139713-URG-B-0123

Copyright © 2023 by Johnson Controls, Inc. All rights reserved.

Supersedes: 6139713-URG-A-0422

York International Corp.

 

5005 York Drive 

Norman, OK 73069

Quick Reference Guide

Standard ECM modular multi-position 

residential air handlers

Reviews: