47
5.3.4
Variables
5.3.4.1
Commands
Register
hex. no.
Register
decimal
no.
Description
Format
Type
Adjustable values
Registers accessible in read-only mode (function 1) and write mode (function 5)
0x118
280
Remote on/off command
Boolean
Read-only/Write
0: Off/1: On
0x119
281
Fault acknowledgement
Boolean
Read-only/Write
0: No/1: Acknowledgement
0x11A
282
Electric heater load shedding
Boolean
Read-only/Write
0: Free / 1: Load shedding
0x11B
283
Unit actuation at eco/comfort temperature
Boolean
Read-only/Write
0: Comfort / 1: Eco
0x11C
284
Unit actuation at eco/comfort flow rate
Boolean
Read-only/Write
0: Comfort / 1: Eco
0x11D
285
Unit actuation at eco/comfort pressure
Boolean
Read-only/Write
0: Comfort / 1: Eco
5.3.4.2
Setpoints
Register
hex. no.
Register
decimal
no.
Description
Format
Type
Adjustable values
Dampers accessible in read-only mode (functions 3 or 4) and write mode (functions 6 for char or 16)
0x0190
400
Supply air fan Comfort flow rate setpoint value
Integer
Read-only/Write
m3/h /10
0x0191
401
Return air fan Comfort flow rate setpoint value
Integer
Read-only/Write
m3/h /10
0x0192
402
Supply air fan Eco flow rate setpoint value
Integer
Read-only/Write
m3/h /10
0x0193
403
Return air fan Eco flow rate setpoint value
Integer
Read-only/Write
m3/h /10
0x0195
405
Supply air duct Comfort pressure setpoint value
Integer
Read-only/Write
Pa
0x0196
406
Supply air duct Eco pressure setpoint value
Integer
Read-only/Write
Pa
0x019A
410
Comfort heating regulated temperature setpoint value
Integer
Read-only/Write
°C x10
0x019B
411
Eco heating regulated temperature setpoint value
Integer
Read-only/Write
°C x10
0x019C
412
Supply air temperature maximum limit value
Integer
Read-only/Write
°C x10
0x019D
413
Supply air temperature minimum limit value
Integer
Read-only/Write
°C x10
0x1A1
417
Air quality control setpoint
Integer
Read-only/Write
ppm
0x1A2
418
Supply air fan maximum flow rate value for air quality
regulation
Integer
Read-only/Write
m3/h /10
0x1A6
422
Cooling Comfort regulated temperature setpoint
Integer
Read-only/Write
°C x10
0x1A7
423
Cooling Eco regulated temperature setpoint
Integer
Read-only/Write
°C x10
0x1A8
424
Heating Comfort regulated temperature setpoint
Integer
Read-only/Write
°C x10
0x1A9
425
Heating Eco regulated temperature setpoint
Integer
Read-only/Write
°C x10
0x1AC
428
Cooling Comfort supply air temperature setpoint
Integer
Read-only/Write
°C x10
0x1AD
429
Cooling Eco supply air temperature setpoint
Integer
Read-only/Write
°C x10
0x1AE
430
Heating Comfort supply air temperature setpoint
Integer
Read-only/Write
°C x10
0x1AF
431
Heating Eco supply air temperature setpoint
Integer
Read-only/Write
°C x10
0x1B4
436
Frost protection setpoint value when the unit is in
Standby
Integer
Read-only/Write
°C x10
0x1B9
441
Temperature control setpoint in "Night cooling" mode
Integer
Read-only/Write
°C x10
0x1BA
442
Duct pressure control setpoint in "Night cooling" mode
Integer
Read-only/Write
Pa
0x1BB
443
Supply air fan flow rate control setpoint in "Night
cooling" mode
Integer
Read-only/Write
m3/h /10