If coil 2 is configured as Mixed, the action on its valve will be limited to prevent a drift in the temperature for the return network to
the heat pump.
If there is a fault with the heat pump (information received via a potential-free (dry) contact), an alarm will be displayed.
1.6.8
Plate recovery
A differential pressure switch is used to check the fouling level on the return side of the heat recovery unit and to manage the frost
protection safety function when the unit is running. This safety function activates the bypass damper.
This damper is also activated if there is a Free cooling request.
1.6.9
Electric heater
In case of a problem on the electric heater (safety thermostats), the electric heater is shut off and the fault is signalled.
Load shedding of the electric heater via the input ID6 is available (function also available through communication with the CMS).
The aim is to use the same input ID1 to control either:
This control principle does not cause an alarm to be created.
1 or 2 stages
Triac + 1 stage
Network T°
Cooling mode
authorised
10
40
Heating mode
authorised
Cooling and heating modes
prohibited
band
band
Heating requirement (%)
Stage 2
100
0
50
Stage 1
Electric heating requirement
(%)
Stage 2
100
0
Stage 1
50