16
When the temperature drops, the controller will calculate the heat requirement needed to keep this temperature constant.
This gradually adjusts the output of the 2 heating coils (via a 3-way valve for coil 1, via a triac or using 1 or 2 stages in the
case of an electric heater) or a "Mixed" type in heating mode (authorised by the water network temperature sensor for coil 2
only).
The order in which the various heat generators are activated can be configured.
Coils available to meet the heating requirements
Heating coil
Mixed water coil
Electric heater
By increasing the regulated temperature, the controller will calculate the exact cooling requirement.
If conditions permit, it will authorise Free Cooling then gradually adjust the output of the cooling coil (via a three-way valve),
"Mixed" type in cooling mode (authorised by the water network temperature sensor for coil 2 only) or DX type (direct
expansion) and will request that the condensation unit starts up when the level of demand from the coil reaches 66%
(adjustable) and that it stops when the demand is 33% (adjustable).
If Free Cooling is disabled, the requirement will be taken over by the coil.
The distribution of the requirement between the Free Cooling and the coil is adjustable.
BM
Y
B
A
B
A
T°C
S
BC
BC
B
A
B
A
Y
Heating requirement (%)
50
100
0
Cooling requirement (%)
50
100
0
Cooling requirement (%)
50
100
0
C
onde
ns
a
ti
o
n
uni
t f
or
t
he
D
X
co
il
66%
Summary of Contents for AirCompact Control
Page 1: ...NA 13 12 B 03 2015 AirCompact Control AirCompact Control manual...
Page 61: ...61...
Page 68: ...68...