45
5.2
The datapoint database
The unit comes with a communication database that includes the most important datapoints for the program, from the values of the
sensors to the parameters displayed in the masks. The database contains three types of datapoint: digital datapoints, integer
datapoints and analogue datapoints. The tables below list the names of these datapoints, their addresses and types (read-only (R)
or read/write (R/W)).
5.3
Modbus
5.3.1
Modbus RTU connection diagram
5.3.2
RS485 connection close-up
Pin
Description
1
GND
2
RX+/TX+
3
RX-/TX-
The components required for connection to the remote and/or local ModBus supervision system are as follows:
-
An RS485 serial card (CIAT code:
7119749
) connected to each controller.
-
A standard RS485/USB converter for connection to a PC (not supplied by CIAT). The converter can be connected to any
network RS485 card.
-
An electrical network using an
AWG20/22
shielded cable (not supplied by CIAT) comprising a twisted pair and shielding
with a max length of
1000 m
. This network must never run parallel to power cables at a distance of less than
50 cm
.
These cables may cross, but perpendicularly. You are requested not to form a loop with the network cable or the earth
braid, and to properly separate the various cable families (control, power, earth and communication bus).
-
A supervision program installed on a PC (not supplied by CIAT).
An 120Ω ¼W electrical resistor must be connected to the RS485 serial card in last position on the bus, as shown in the connection
diagram.
The format of the data frame, which cannot be modified, is as follows: 8 data bits, 2 stop bits and without parity on 2 words (2
bytes), high-order, low-order.
The data format (16 bits, signed) is standard for Modbus except for analogue data which is in the format "Integer divided by 10"