58
optimisation" mode
Control setpoint
return for the
monitored Eco
Heating temperature
in "Energy
optimisation" mode
WTempRegulEcoChaud
DPT_Value_Temp
9.001
OUT
425
REG
Control setpoint for
the Comfort Cooling
supply air temperature
in "Energy
optimisation" mode
WTempSoufflConfortFroid
DPT_Value_Temp
9.001
IN
428
REG
Control setpoint
return for the Comfort
Cooling supply air
temperature in
"Energy optimisation"
mode
WTempSoufflConfortFroid
DPT_Value_Temp
9.001
OUT
428
REG
Control setpoint for
the Eco Cooling
supply air temperature
in "Energy
optimisation" mode
WTempSoufflEcoFroid
DPT_Value_Temp
9.001
IN
429
REG
Control setpoint
return for the Eco
Cooling supply air
temperature in
"Energy optimisation"
mode
WTempSoufflEcoFroid
DPT_Value_Temp
9.001
OUT
429
REG
Control setpoint for
the Comfort Heating
supply air temperature
in "Energy
optimisation" mode
WTempSoufflConfortChaud
DPT_Value_Temp
9.001
IN
430
REG
Control setpoint
return for the Comfort
Heating supply air
temperature in
"Energy optimisation"
mode
WTempSoufflConfortChaud
DPT_Value_Temp
9.001
OUT
430
REG
Control setpoint for
the Eco Heating
supply air temperature
in "Energy
optimisation" mode
WTempSoufflEcoChaud
DPT_Value_Temp
9.001
IN
431
REG
Control setpoint
return for the Eco
Heating supply air
temperature in
"Energy optimisation"
mode
WTempSoufflEcoChaud
DPT_Value_Temp
9.001
OUT
431
REG
Unit reactivation
setpoint in "Standby"
mode when there is an
ambient temperature
sensor
WTempHorsGel
DPT_Value_Temp
9.001
IN
436
REG
Unit reactivation
setpoint return in
"Standby" mode when
there is an ambient
temperature sensor
WTempHorsGel
DPT_Value_Temp
9.001
OUT
436
REG
Control setpoint in
"Night cooling" mode
WTempNocturne
DPT_Value_Temp
9.001
IN
441
REG
Control setpoint
return in "Night
cooling" mode
WTempNocturne
DPT_Value_Temp
9.001
OUT
441
REG
Unit operating state
0 = off
1 = on
2 = on after power
failure
3 = standby
4 = off by a fault
5 = off by CMS
6 = post ventilation
EtatUnite
DPT_Value_2_Ucount
7.001
OUT
1280
REG
Alarm 1 value:
Alarme1
DPT_Value_2_Ucount
7.001
OUT
27