48
0x1BC
444
Return air fan flow rate control setpoint in "Night
cooling" mode
Integer
Read-only/Write
m3/h /10
0x1BD
445
Stage 1 and off setpoint value for the electric heater
Integer
Read-only/Write
%
0x1BE
446
Stage 1 on setpoint value for the electric heater
Integer
Read-only/Write
%
0x1BF
447
Stage 2 off setpoint value for the electric heater
Integer
Read-only/Write
%
0x1C0
448
Stage 2 on setpoint value for the electric heater
Integer
Read-only/Write
%
0x1C4
452
Free Cooling authorisation limit setpoint value in
relation to the fresh air temperature
Integer
Read-only/Write
°C x10
0x1C5
453
Value of the minimum % of fresh air during Free
cooling management
Integer
Read-only/Write
%
0x1D0
464
High threshold for supply air filter CF1 fouled fault
Integer
Read-only/Write
Pa
0x1D1
465
High threshold for supply air filter CF1 clogged fault
Integer
Read-only/Write
Pa
0x1D5
469
High threshold for return air filter CF1 fouled fault
Integer
Read-only/Write
Pa
0x1D6
470
High threshold for return air filter CF1 clogged fault
Integer
Read-only/Write
Pa
0x1DB
475
Stage off setpoint value for the DX coil
Integer
Read-only/Write
%
0x1DC
476
Stage on setpoint value for the DX coil
Integer
Read-only/Write
%
0x1E5
485
Changeover limit setpoint value in Heating mode and
water return temperature
Integer
Read-only/Write
°C x10
0x1E6
486
Changeover limit setpoint value in Cooling mode and
water return temperature
Integer
Read-only/Write
°C x10
0x1E7
487
Value for the water return temperature control
proportional band
Integer
Read-only/Write
°C x10
0x1EB
491
Duct pressure sensor fault low threshold
Integer
Read-only/Write
Pa
0x1EC
492
Duct pressure sensor fault high threshold
Integer
Read-only/Write
Pa